Honeywell TB6575 SuitePRO Installation Instructions Manual page 11

Digital fan coil thermostats
Hide thumbs Also See for TB6575 SuitePRO:
Table of Contents

Advertisement

SETUP
IS
Code
Option
Code
Description
Value
11
CPH Value
1 to 12 Range is 1 to 12. Default is 4.
for Heat
12
CPH Value
1 to 6 Range is 1 to 6. Default is 3.
for Cool
13
CPH for
1 to 12 Range is 1 to 12. Default is 6.
Auxiliary
Electrical
Heater
14
Display
-4 to 4 Range is -4°F to +4°F; Default is 0°F.
Temperature
Adjustment
15
Temperature
0
Display
1
Mode
2
16
Setpoint
50 to 90 Range is 50°F to 90°F. Default is 90°F.
Range Stop
for Heating
17
Setpoint
50 to 90 Range is 50°F to 90°F. Default is 50°F.
Range Stop
for Cooling
18
Keypad
0
Lockout
1
2
3
19
Remote
0
Setback
1
2
3
4
20
Remote
50 to 70 Range is 50°F to 70°F. Default is 64°F.
Setback for
Heating
21
Remote
72 to 90 Range is 72°F to 90°F. Default is 79°F.
Setback for
Cooling
22
Activity
0
Sensing
1
2
3
TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
Table 4. Installer Setup (IS) Codes and Options. (Continued)
Option Description (Default value shown in Bold)
Display Room Temperature
Display Setpoint
Display Temperature and Setpoint; Default.
All keys are available; Default
The System button (Heat/Cool) is locked out
Both the System and Fan buttons are locked out.
All buttons are locked out (System, Fan, Up Arrow, and Down
Arrow). The LCD displays
Disabled; Default
Hotel card enabled N.O. with
1 second software delay going from UnOccupied to Occupied;
2 minute delay going from Occupied to UnOccupied.
Hotel Card enabled N.C. with
1 second software delay going from UnOccupied to Occupied;
2 minute delay going from Occupied to UnOccupied.
Hotel Card enabled N.O. with
1 second software delay going from UnOccupied to Occupied;
30 minute delay going from Occupied to UnOccupied
Hotel Card enabled N.C. with
1 second software delay going from UnOccupied to Occupied;
30 minute delay going from Occupied to UnOccupied.
Disabled; Default
4 hour sensing
12 hour sensing
24 hour sensing
.
LOCKeD
11
Notes
The number selected indicates the
maximum times Heating is cycled on
per hour (CPH).
The number selected indicates the
maximum times Cooling is cycled on
per hour (CPH).
The number selected indicates the
maximum times Auxiliary Heating is
cycled on per hour (CPH).
Used when the thermostat is in the
Unoccupied state.
Anytime the thermostat is not
touched (no single key is pressed) for
the duration selected, the thermostat
automatically falls back into the
Unoccupied setpoints. When any key
is pressed, the thermostat controls to
Occupied mode
NOTE: IS code #19 (Remote Set-
back) must be disabled
(value = 0) in order to dis-
play the Activity Sensing
code.
62-0278—01