Troubleshooting; Check Methods - Mitsubishi Electric PEFY-P20VMS-E Technical & Service Manual

Hide thumbs Also See for PEFY-P20VMS-E:
Table of Contents

Advertisement

[ VII Troubleshooting ]
VII Troubleshooting

[1] Troubleshooting

1. Check methods

1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
Normal
4.3k
- 9.6k
(Refer to the thermistor characteristic graph below.)
1) Thermistor characteristic graph
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Drain sensor (DS)
Thermistor R
= 15 k
0
Multiplier of B = 3480 k
1
Rt = 15 exp { 3480(
273+t
0°C 15k
10°C 9.6k
20°C 6.3k
25°C 5.2k
30°C 4.3k
40°C 3.0k
(A) Temperature
(°C)
(B) Resistance
(k )
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
CN60
(F)
1
(E)
2
White-Red
(D)
3
LEV
(C)
4
(B)
5
(A)
6
(A)
Brown
(D)
(B)
Red
(E)
(C)
Blue
(F)
Abnormal
Open or short
50
3%
40
2%
1
) }
273
30
20
10
0
Normal
1-5
2-6
Yellow-Brown
200 k
Orange
Yellow
White
-20
-10
0
10
20
30
(A)
3-5
4-6
Orange-Red
Blue-Brown
10%
- 11 -
40
50
Abnormal
Open or short

Hide quick links: