CP EBDSPIR-DD-LV Product Manual

Ceiling pir presence detector-dali/dsi 12-24v ac/dc

Advertisement

Quick Links

EBDSPIR-DD-LV
Ceiling PIR presence detector - DALI / DSI 12-24V AC/DC
Front features
Mounting Bezel
Back features
Retaining Spring
Power Input
& Switched
Output Connector
(Channel 1)
Retaining Spring
Product Guide
The EBDSPIR-DD-LV PIR (passive infrared) presence
detector provides automatic control of low voltage loads
including lighting and BMS systems with optional manual
control.
Output Channel 1 comprises a relay capable of simple on/
off switching, while Output Channel 2 provides dimmable
control of either DALI or DSI type ballasts.
Functioning as a presence detector, the unit can turn lights
on when a room is occupied and off when the room is
empty. Optional settings allow lights to be turned off in
response to ambient daylight, or to implement a maintained
illuminance (daylight harvesting) system.
The flexibility of having two channels and two switch inputs
allows the following example scenarios:
All functionality is fully programmable using an IR handset.
PIR Sensor
Detects movement within the unit's detection range,
allowing load control in response to changes in occupancy.
IR Receiver
Receives control and programming commands from an
IR (infrared) handset.
Light Level Sensor
Measures the overall light level in the detection area
Status LEDs
Sensor Lens
which covers...
The LED flashes Red to indicate the following:
PIR Sensor
Walk Test LED active
IR Receiver
Light Level Sensor
Valid setting received
Status LEDs
Power Input & Switched Output Connector (Channel 1)
Used to connect power to the unit and to connect a
switched load.
Dimmable Control Output Connector (Channel 2)
Used to connect DSI/DALI controllable ballasts and
Dimmable
transformers for dimmable loads.
Control Output
Connector
Switch Input Connector
(Channel 2)
Two input terminals can be used to manually override the
dimming levels and override the lights on or off.
Switch Input
Connector
Dim an outside row of luminaires whilst internal fittings
are switched
Provide absence detection for two separate channels
Maintained illuminance system with manual up/down
controls
Overview
Features
when movement is detected

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EBDSPIR-DD-LV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CP EBDSPIR-DD-LV

  • Page 1 Product Guide EBDSPIR-DD-LV Ceiling PIR presence detector - DALI / DSI 12-24V AC/DC Overview The EBDSPIR-DD-LV PIR (passive infrared) presence detector provides automatic control of low voltage loads including lighting and BMS systems with optional manual control. Output Channel 1 comprises a relay capable of simple on/ off switching, while Output Channel 2 provides dimmable control of either DALI or DSI type ballasts.
  • Page 2 Detection diagram Area of high sensitivity Area of lower sensitivity...
  • Page 3: Installation

    It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time to guarantee lamp life (refer to the manufacturer’s datasheet for details). As this EBDSPIR-DD-LV is able to dim the lamps using DALI/DSI, the product provides a facility to disable this for a given period of time.
  • Page 4 Installation The EBDSPIR-DD-LV is designed to be mounted using either:  Flush fixing, or  Surface fixing, using the optional Surface Mounting Box (part no. DBB). Both methods are illustrated below. Flush Fixing Hole Ø64mm Warning - be careful bending springs when mounting unit.
  • Page 5: Wiring Diagrams

    Wiring diagrams Channel 1 (switched output) of the EBDSPIR-DD-LV Channel 2 (dimmable output) of the EBDSPIR-DD-LV can provides a switched low voltage output which can be used be used to control the light output of luminaires that are to power a mains load via an auxiliary relay or for other fitted with dimming ballasts/transformers.
  • Page 6 PUSH TO MAKE SWITCH Optional for presence, DOWN mandatory for absence detection SWITCH 2 - MOMENTARY PUSH TO MAKE SWITCH Optional for presence, EBDSPIR-DD-LV SENSOR mandatory for absence detection LOAD CONNECTIONS LOAD CONNECTIONS -DD-LV -DD-LV/OC -DD-LV/GOLD Two channel, common switch...
  • Page 7: Fault Finding

    Power-up test procedure When power is applied to the unit, the load will turn on immediately. Set the timeout to 10 seconds, vacate the room or remain very still and wait for the load to switch off . Check that the load switches on when movement is detected. The unit is now ready for programming.
  • Page 8: Basic Programming

    Basic programming The functionality of the EBDSPIR-DD-LV is controlled by a number of parameters which can be changed or programmed by any of the following devices:  UHS5 Infrared Handset. See below for programmable functions.  UNLCDHS Infrared Handset (with LCD). See user guide for full programming details.
  • Page 9: Advanced Programming

    Advanced programming UHS5 UNLCDHS Parameter Name Default Value Range / Options Description Detector Parameters When set to On this causes a red LED to flash on the sensor when it detects   Walk Test LED On or Off movement. Use this feature to check for adequate sensitivity levels. Time Out 20 minutes 0-99 minutes...
  • Page 10 Advanced programming UHS5 UNLCDHS Parameter Name Default Value Range / Options Description Channel 1 –Switching Channel   Detection Mode Presence Presence or Presence mode allows the output to turn on when movement is detected and off when movement ceases. Absence mode allows the output to turn off when Absence movement ceases, but must be manually turned on first.
  • Page 11 This page intentionally left blank...
  • Page 12: Technical Data

    + 44 (0) 333 900 0671 Fax: + 44 (0) 333 900 0674 www.cpelectronics.co.uk enquiry@cpelectronics.co.uk Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice. Ref: #WD488 Issue 3...