Fujitsu ARU9RLF Design & Technical Manual page 16

Hide thumbs Also See for ARU9RLF:
Table of Contents

Advertisement

MODEL
: ARU18RLF
AFR
°FDB
-5
5
14
23
32
41
47
50
59
AFR : Air Flow Rate (CFM)
TC : Total Capacity (kBtu/h)
IP : Input Power (kW)
AFR
°CDB
-20.6
-15.0
-10.0
-5.0
0.0
5.0
8.3
10.0
15.0
3
AFR : Air Flow Rate (m
/min)
TC : Total Capacity (kW)
IP : Input Power (kW)
554
°FDB
60
°FWB
TC
IP
-7
19.3
2.42
3
20.7
2.63
12
22.2
2.68
19
23.1
2.79
28
23.3
3.02
37
25.5
2.67
43
26.9
2.50
47
29.7
2.23
50
30.8
2.24
15.7
°CDB
15.6
°CWB
TC
IP
-21.7
5.67
2.42
-16.1
6.08
2.63
-11.1
6.50
2.68
-7.2
6.78
2.79
-2.2
6.84
3.02
2.8
7.47
2.67
6.1
7.88
2.50
8.3
8.71
2.23
10.0
9.02
2.24
- (01 - 13) -
Indoor temperature
65
70
TC
IP
TC
IP
18.9
2.47
18.4
2.52
20.2
2.68
19.7
2.74
21.6
2.73
21.1
2.79
22.6
2.85
22.0
2.91
22.8
3.08
22.2
3.14
24.9
2.73
24.3
2.78
26.2
2.55
25.6
2.60
29.0
2.28
28.3
2.32
30.1
2.29
29.3
2.34
Indoor temperature
18.3
21.1
TC
IP
TC
IP
5.53
2.47
5.40
2.52
5.93
2.68
5.79
2.74
6.34
2.73
6.19
2.79
6.62
2.85
6.45
2.91
6.68
3.08
6.51
3.14
7.29
2.73
7.12
2.78
7.69
2.55
7.50
2.60
8.50
2.28
8.29
2.32
8.81
2.29
8.59
2.34
75
TC
IP
17.5
2.63
18.8
2.85
20.1
2.90
20.9
3.03
21.1
3.19
23.1
2.90
24.3
2.70
26.9
2.42
27.9
2.43
23.9
TC
IP
5.13
2.63
5.50
2.85
5.88
2.90
6.13
3.03
6.19
3.19
6.76
2.90
7.13
2.70
7.88
2.42
8.16
2.43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aru12rlfAru18rlfAou9rlfcAou12rlfcAou18rlfc

Table of Contents