Daikin REYQ72TTJU Installation Manual page 34

Vrv iv
Table of Contents

Advertisement

NOTE
• The refrigerant charging port is connected to the piping inside the
unit. The unit's internal piping is already factory charged with refrig-
erant, so be careful when connecting the charge hose.
• After adding the refrigerant, do not forget to close the lid of the
refrigerant charging port. The tightening torque for the lid is 8.48 to
10.3 ft
lbf (11.5 to 13.9 N
m).
• In order to ensure uniform refrigerant distribution, it may take the
compressor ±10 minutes to start up after the unit has started opera-
tion. This is not a malfunction.
A:
Adding refrigerant by using the automatic charging function
INFORMATION
The automatic refrigerant charging has limits as described below. Out
of these limits, the system cannot operate the automatic refrigerant
charging:
• Outdoor temperature: 32°F (0°C) DB -109°F (43°C) DB.
• Indoor temperature: 50°F (10°C) DB - 89°F (32°C) DB.
• Total indoor unit capacity: ≥ 80%
6a The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the automatic refrigerant
charge operation mode.
Depending on the ambient limitation conditions (see above), the
unit will automatically decide which operation mode will be used
to fulfill the automatic refrigerant charge: cooling or heating. If
above conditions are fulfilled, cooling operation will be selected. If
not, heating mode will start.
Procedure
• Idle (default) screen is shown.
• Push BS2 once, indication
• Push BS2 for more than 5 seconds, wait while the unit is
preparing for operation. Segment display indication:
sure control is executed):
- In case heating operation is started: indication
will be displayed (start up control; waiting stable heating
operation).
- In case cooling operation is started: indication
will be displayed (start up control; waiting stable cooling
operation).
23
03
• When
or
starts flashing (ready for charging), push
BS2 within 5 minutes. Open valve A. If BS2 is not pushed within
5 minutes, a malfunction code will appear:
26
- Heating operation:
the procedure.
- Cooling operation: malfunction code
Push BS1 to abort and restart the procedure.
Heating (middle segment indicates
Charging will continue, the segment indication intermittently
shows the current low pressure value and the status indication
23
.
When the remaining additional refrigerant amount is charged,
close valve A immediately and push BS3 to stop charging opera-
tion.
After BS3 is pushed, the ending code
is pushed, the unit will check whether the ambient conditions are
favorable to execute the test run.
01
02
03
- If
,
, or
appears, push BS1 to finish the auto-
matic charging function procedure. The ambient conditions
are favorable to execute the test run.
31
888
.
01
(pres-
22
23
till
02
03
till
will be flashing. Push BS2 to restart
P2
will appear.
2
)
26
will appear. When BS2
E-2
- If the unit indicates
, or
NOT favorable to execute the test run. Push BS1 to finish the
automatic charging procedure.
INFORMATION
In case a malfunction code occurred during this automatic charging
procedure, the unit will stop and indicate
restart the procedure.
Cooling (middle segment indicates
Automatic charging will continue, the segment indication shows
the current low pressure value and the status indication
intermittent.
If the segment indication/user interface of indoor unit shows
code, charging is almost finished. When the unit stops operating,
close valve A immediately and check whether the segment indi-
cation/user interface of indoor unit shows
automatic charging in cooling program was finished successfully.
INFORMATION
When the charging amount is little, the
P9
but instead the
code will be displayed immediately.
When the required (calculated) additional refrigerant amount is
PE
P9
already charged before
or
indication appears, close valve A and
P9
wait till
is displayed.
If during the cooling operation for the automatic refrigerant charge
the ambient conditions go beyond the allowable for this operation
mode, the unit will indicate on the segment display the code
in case indoor temperature is out of range or
door temperature is out of range. In this case, when the additional
refrigerant charging was not finished, step 6a has to be repeated.
INFORMATION
• When a malfunction is detected during the procedure (e.g, in case
of closed stop valve), a malfunction code will be displayed. In that
case, refer to 15.5. Malfunction code list on page 40 and solve
the malfunction accordingly. Resetting the malfunction can be done
by pushing BS1. The procedure can be restarted from 6a.
• Aborting the automatic refrigerant charge is possible by pushing
BS1. The unit will stop and return to idle condition.
Perform the test procedure as described in 15.4.2. Test operation on
page 39.
B:
Adding refrigerant by using the manual charging function
6b The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the manual refrigerant
charge operation mode:
• Turn on the power of the indoor units and outdoor unit.
• Take all the precautions mentioned in start-up and configura-
tion into account.
• Activate outdoor unit setting [2-20]=1 to start manual refriger-
ant charge mode. Refer to page 34 for details.
Result: The unit will start operation. Valve A can be opened.
Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount is
added, close valve A and push BS3 to stop the manual refrig-
erant charging procedure.
INFORMATION
The manual refrigerant charge operation will automatically stop within
30 minutes. If charging is not completed after 30 minutes, perform the
additional refrigerant charging operation again.
E-3
, the ambient conditions are
26
flashing. Push BS2 to
0
)
03
PE
P9
. This indicates the
PE
code may not be displayed,
E-2
E-3
in case the out-
3P362438-3H English