Applies to
Attribute
Data Types
HI_HI Limit
analog
HI_HI
analog
Priority
HI Enabled
analog
HI Limit
analog
HI Priority
analog
LO Enabled
analog
LO Limit
analog
LO Priority
analog
LO_LO
analog
Enabled
LO_LO Limit
analog
LO_LO
analog
Priority
Discrete
discrete,
Enabled
bit array
Determines the value, in engineering units, that invokes a
HI_HI alarm condition. The tag alarm state remains HI_HI
until the tag value goes below the HI_HI alarm limit minus
the alarm deadband.
Determines the value (between 1 and 15) for the alarm priority
for the HI_HI alarm, where 15 represents the highest priority.
Determines whether to enable HI alarms for a tag.
Determines the value, in engineering units, that invokes a HI
alarm condition. The tag alarm state remains HI until the tag
value goes below the HI alarm limit minus the alarm deadband.
Determines the value (between 1 and 15) for the alarm priority
for the HI alarm, where 15 represents the highest priority.
Determines whether to enable LO alarms for the tag.
Determines the value, in engineering units, that invokes a LO
alarm condition. The tag alarm state remains LO until the tag
value goes above the LO alarm limit plus the alarm deadband.
Determines the value (between 1 and 15) for the alarm priority
for the LO alarm, where 15 represents the highest priority.
Determines whether to enable LO_LO alarms for a tag.
Determines the value, in engineering units, that invokes
a LO_LO alarm condition. The tag alarm state remains
LO_LO until the tag value goes above the LO_LO alarm
plus the alarm deadband.
Determines the value (between 1 and 15) for the alarm priority
for the LO alarm, where 15 represents the highest priority.
Determines whether to enable tag value alarms for discrete and
bit array tags.
Description