KEPCO RKW 3.3-7K Instruction Manual

30 watt single output open frame power supplies

Advertisement

Quick Links

I N S T R U C T I O N M A N U A L
KEPCO
I — INTRODUCTION
SCOPE OF MANUAL. This instruction manual covers
the installation and operation of the Kepco RKW 30W
Series of Open Frame, RoHS (Reduction of Hazardous
Substances) compliant, switching power supplies.
DESCRIPTION. The Kepco RKW 30W Series consists of
six models of switching power supplies, with a single output
as shown in Table 1. Units may be operated with a nominal
100V a-c to 240V a-c (input voltage range 85 to 265 Va-c),
50-60 Hz
(input frequency range 47-66Hz; units operate up to
440Hz although leakage current and efficiency specifications may
They will also operate on 110V to 370V d-c
not be met).
input. The RKW 30W Series employs a MOSFET switch
flyback converter with a fixed switching frequency of
approximately 60kHz. Regulation is provided by pulse
MODEL
OUTPUT VOLTS, d-c
ADJUSTMENT RANGE, Vd-c
OUTPUT CURRENT (AMPS)
-10 to +50 °C
(1)
CURRENT LIMIT
(AMPS)
(2)
OVP SETTING
(VOLTS)
100 Va-c
EFFICIENCY
200 Va-c
Switching ripple
RIPPLE
(typ)
AND
(3)
NOISE
spike noise
(mV p-p)
(typ)
(1)
After the cause of the overload is removed, output is automatically restored.
(2)
An overvoltage shuts down the output. Recover by recycling a-c input (60 second delay required before resetting).
(3)
Bandwidth 100 MHz. Ripple and noise will be approximately 1.5 times these values in the operating temperature range -10 ~ 0°C. The
ripple and noise values tabulated are valid when the output is derated as shown in figure 2 from 50 ~ 65°C.
(4)
Peak Current: 2.0A (useful for motor start applications).
KEPCO, INC.
131-38 SANFORD AVENUE
©2010, KEPCO, INC
Data subject to change without notice
An ISO 9001 Company.
30 WATT SINGLE OUTPUT
OPEN FRAME POWER SUPPLIES
TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RKW 30W SERIES
RKW 3.3-7K
RKW 5-6K
3.3V
2.85-4.0
7.0
7.9 min
4.2-5.2
75%
76%
80
120
(1)
FLUSHING, NY. 11355 U.S.A.
http://www.kepcopower.com
width modulation. A thermistor prevents excessive turn-on
current surge. Overvoltage and overcurrent protection is
provided. Current limiting with automatic recovery from
short circuit is featured. Units are convection cooled L-
chassis construction. A steel cover (Model CA 33-R) is
available as an option (contact factory for derating with
cover).
Specifications and operating limits for individual RKW 30W
models are listed in Table 1. Section II describes RKW 30W
features. Section III contains specifications and operating
limits common to all RKW 30W Series Models. Section IV
describes installation and Section V describes operation.
RKW 12-2.5K
5V
12V
4.0-5.8
9.6-13.2
6.0
2.5
6.3 min
2.6 min
6.0-6.9
13.7-15.7
77%
81%
78%
82%
80
100
120
150
email: hq@kepcopower.com
228-1449 REV 5
RKW
30W SERIES
RKW 15-2K
RKW 24-1.3K
15V
24V
12-16.5
19.2-26.4
(4)
2.0
1.3
2.1 min
2.1 min
17.0-19.0
27.0-30.5
81%
84%
83%
85%
100
100
150
150
TEL (718) 461-7000
FAX (718) 767-1102
RKW 48-0.65K
48V
38.4-52.8
0.65
0.68 min
55.0-60.0
84%
85%
130
200
1

Advertisement

loading

Summary of Contents for KEPCO RKW 3.3-7K

  • Page 1 I — INTRODUCTION SCOPE OF MANUAL. This instruction manual covers width modulation. A thermistor prevents excessive turn-on the installation and operation of the Kepco RKW 30W current surge. Overvoltage and overcurrent protection is Series of Open Frame, RoHS (Reduction of Hazardous provided.
  • Page 2: Specifications

    See Table 1. The overvoltage circuit is set by Zener diode Combined effect: 0.9% typ., 1.8% max. clamp, latching will occur. Drift: (1/2 to 8 hr. at 25°C) 0.2% typ., 0.5% max. KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102 http://www.kepcopower.com...
  • Page 3: Emc - Emissions

    AC input Neutral, Line and Ground wires to must not exceed the ambient values given in the graph in the respective terminals of the terminal block (see Figure Figure 1. KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102 http://www.kepcopower.com...
  • Page 4: Operation

    NEUTRAL nected to the power supply output terminals to protect the unit from reverse voltage. FIGURE 2. COMPONENT LOCATIONS FIGURE 3. POWER SUPPLY MOUNTING KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102 http://www.kepcopower.com email: hq@kepcopower.com...
  • Page 5 FIGURE 4. RKW 30W MECHANICAL OUTLINE DIAGRAM KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102 http://www.kepcopower.com email: hq@kepcopower.com 082610 228-1449 REV 5...