Sequence Of Operation; Cooling Mode; Heating Mode - Bosch TW Series Installation, Operation And Maintenance Manual

Water to water
Hide thumbs Also See for TW Series:
Table of Contents

Advertisement

TW Series Water to Water

SEQUENCE OF OPERATION

Cooling Mode

Energizing the "O" terminal energizes the unit reversing
valve thus placing the unit into cooling mode. T
When the thermostat calls for first stage cooling (Y1) the
loop pump or solenoid valve if present is energized and
the first stage of compressor capacity starts.
When the thermostat calls for second stage cooling (Y2)
the second stage (or full compressor capacity) is
initiated. Once the thermostat is satisfied, the
compressor shuts down accordingly

Heating Mode

The first two stages of heating (Y1 & Y2) operate in the
same manner as cooling, but with the reversing valve de-
energized. Once the thermostat is satisfied, the
compressor shuts down,
Revised 02-16
NOTE: Diagram for illustration purposes only.
Ensure access to Heat Pump is not restricted.
Figure # 7
Sequence of operation | 11
6720220047 (2016/02)