Rinnai Q Premier QP85N Installation & Servicing Instructions Manual page 75

High effi ciency condensing gas boiler
Hide thumbs Also See for Q Premier QP85N:
Table of Contents

Advertisement

Code
Description
contact for return sensor T2
open
Control unit error
Control unit error
Electrical leakage to ground.
No software present
Ribbon cable problem
Flue gas temperature to high
(adjustment parameter 84 -
default 212°F)
Fuse on controller PCB
defective
or
Cable transformer not
connected
Solution
Check the data in Error mode. Boiler data during error:
1 Error
= 37
2 Operational status = 00
3 Flow temp.
= xx*
4 Return temp.
= -22
5 kW burner
= 00**
6 % pomp
= xx*
* = variable values
**= x3415=BTU/hr
Check the wiring. check the wiring for the sensor
The wiring is OK but the error is repeated. Remove the plug from the fl ow
sensor as a result of which Error 32 occurs
Replace the sensor.
Software error control unit. Replace the control unit. The display will
automatically load the program into the new control unit.
Software error control unit. Replace the control unit. The display will
automatically load the program into the new control unit.
Moisture on controller PCB. Check if there is water leaking on or in the
boiler.
Stop water leak and replace controller
Control unit and display don't have a programm. There are a new display
and a new control unit installed at the same time. Exchange the parts and
the loading will start automatically and
Replace ribbon cable
Replace fl ue sensor or adjust parameter 84 to default
Replace fuse.
A 4A and 5A spare fuse can be found inside the Control Tower just above
the circuit board.
appears on the display.
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q premier qp130n

Table of Contents