[ IX Troubleshooting ]
Error
Prelimi-
(prelim-
Error
nary
inary)
Code
error
detail
code
code
5102
1217
-
5103
1205
00
5104
1202
-
5105
1204
-
5106
1216
-
5107
1221
-
5108
1218
-
5112
1215
-
5110
1214
01
5111
-
-
5112
-
-
5115
-
-
5116
-
-
5201
-
-
5201
1402
-
5203
-
-
HWE09080
Error code definition
Indoor unit pipe tempera-
ture (TH22)
Temperature sensor
OA processing unit pipe
fault
temperature (TH2)
HIC bypass circuit outlet
temperature (TH2)
Indoor unit gas-side pipe
temperature (TH23)
OA processing unit gas-
Temperature sensor
side pipe temperature
fault
(TH3)
Pipe temperature at heat
exchanger outlet (TH3)
OA processing unit intake
air temperature (TH1)
Temperature sensor
Outside temperature
fault
(TH24)
Heat source unit discharge
temperature (TH4)
Temperature sensor
Accumulator inlet tempera-
fault
ture (TH5)
Temperature sensor
HIC circuit outlet tempera-
fault
ture (TH6)
Temperature sensor
Water inlet pipe (TH7)
fault
Temperature sensor
Water outlet pipe (TH8)
fault
Temperature sensor
Component cooler heat ex-
fault
changer outlet (THINV)
Temperature sensor
Heatsink temperature
fault
(THHS)
Liquid inlet temperature
(TH11)
Bypass outlet temperature
Temperature sensor
(TH12)
fault
LEV3 outlet temperature
(BC controller)
(TH15)
LEV3 inlet temperature
(TH16)
High-pressure sensor fault (63HS1)
High-pressure sensor fault
(Heat source unit HPS/BC controller PS1)
Intermediate pressure sensor fault
(BC controller PS3)
- 228 -
Searched unit
Notes
O
O
O
O
O
O
O
Detectable
only by the All-
O
Fresh type in-
door units
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
GB

Hide quick links: