Mitsubishi Electric PUHY-P200 Service Handbook page 67

City multi
Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

DipSW5-1
DipSW3-9
OFF
Standard specification
High-static pressure
ON
(60Pa) specification
(2) INV board
Switch
Function
SW1
1
Enabling/disabling the following error
detection functions:
ACCT, DCCT sensor circuit error
(530X Detail No. 115, 116)
ACCT, DCCT sensor error
(530X Detail No. 117, 118)
IPM open/Disconnected CNCT2
(530X Detail No. 119)
Detection of erroneous wiring
(530X Detail No. 120)
2
3
4
5
6
SW2
1
Inverter address
2
3
4
Note 1 Except for SW2-1, all are set to OFF at factory shipment.
Unless otherwise specified, set the switch to OFF where indicated by " ––," which may be set to a certain setting for a reason.
Note 2 Leave SW1-1 off during normal operation. If it is turned on, errors cannot be detected and the unit may be damaged.
(3) FAN board
Switch
Function
SW2
1
Inverter address
2
3
4
Note 1 Except for SW2-1, all are set to OFF at factory shipment.
Unless otherwise specified, set the switch to OFF where indicated by " ––," which may be set to a certain setting for a reason.
OFF
ON
Standard specification
High-static pressure
(30Pa) specification
Function according to switch setting
OFF
Error detection enabled
0
Function according to switch setting
OFF
0
- 65 -
ON
OFF
Error detection disabled
Anytime after power on
1
Always leave it to ON
ON
OFF
5
Always leave it to ON
Switch setting timing
ON
Switch setting timing
ON