Panasonic CS-XE9SKUA Service Manual page 81

Indoor/outdoor unit
Hide thumbs Also See for CS-XE9SKUA:
Table of Contents

Advertisement

15.4.27 F99 (DC Peak Detection)
Malfunction Decision Conditions
During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal
DC Peak sensing circuitry.
Malfunction Caused
DC current peak due to compressor failure.
DC current peak due to defective power transistor(s).
DC current peak due to defective outdoor unit PCB.
DC current peak due to short circuit.
Troubleshooting
When abonormality indication starts again.
Reset the error code and turn on the unit
again.
Is there a sound when compressor starts?
Is compressor vibration even?
Is there no change even if all refrigerant
is discharged?
Check the compressor winding resistance:
Turn off the power and disconnect
the harnesses U, V and W.
Measure the winding resistance
between U-V, V-W and W-U.
Are the compressor's winding resistance
(U-V, V-W or U-W) shorted?
NO (Compressor stops)
YES
NO (Quite a lot of vibration at
start operation)
YES
NO (Normal)
YES (Stops after 2, 3 seconds
of noise during operation)
NO (Normal)
YES
Outdoor electronic circuit defect due to
power transistor short.
Replace the outdoor unit PCB.
Amplification IC defect.
Diode defect.
Defect in microcontroller.
Replace the outdoor unit PCB.
Excessive amount of refrigerant.
For safety reason and to prevent component
breakdown, always switch off the power
Caution
before remove and connect the component.
Compressor defective due to
mechanical locked.
Replace compressor.
Compressor defective due to winding
shorted.
Replace compressor.
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-xe12skuaCs-xe12skuaCu-xe9skua

Table of Contents