Drolet Escape 1800 DB03102 Installation And Operation Manual page 32

Hide thumbs Also See for Escape 1800 DB03102:
Table of Contents

Advertisement

Installation and Operation Manual for Escape 1800
Clearances for mobile homes
A
B
C
K
L
If the above clearances are met, then the distances measured from the flue outlet
will be:
D
E
F
*The pipe distances listed in this table refer to the distances obtained when the
stove is installed in accordance with the appliance clearances above mentioned.
However, you can install the stove at reduced clearances; follow the instructions in
Section 7.4: Reducing Wall and Ceiling Clearances Safely. Where they are followed,
the new distance of the pipe to combustible materials must be respected in the
appropriate certification of the pipe.
32
MOBILE HOME APPLIANCE CLEARANCES
(INSTALLATION WITH DOUBLE WALL PIPE
CONNECTOR)
CANADA
14" (356 mm)
19" (483 mm)
13" (330 mm)
48" (1220 mm)
84" (213 cm)
DISTANCES* FROM PIPE CONNECTOR TO THE
COMBUSTIBLE MATERIALS
CANADA
17¾" (451 mm)
29" (737 mm)
24¼" (616 mm)
USA
14" (356 mm)
19" (483 mm)
13" (330 mm)
48" (1220 mm)
84" (213 cm)
USA
17¾" (451 mm)
29" (737 mm)
24¼" (616 mm)