Drolet Escape 1800 DB03102 Installation And Operation Manual page 31

Hide thumbs Also See for Escape 1800 DB03102:
Table of Contents

Advertisement

Installation and Operation Manual for Escape 1800
Clearances with ceiling (L) lowered to 76" (193 cm)
APPLIANCE CLEARANCES
(INSTALLATION WITH SINGLE
WALL PIPE CONNECTOR)
CANADA
A
15" (381 mm)
B
17" (432 mm)
C
14" (356 mm)
K
48" (1220 mm)
L
76" (193 cm)
If the above clearances are met, then the distances measured from the flue outlet
will be:
DISTANCES* FROM PIPE
CONNECTOR TO THE
COMBUSTIBLE MATERIALS
CANADA
D
18¾" (476 mm)
E
27" (686 mm)
F
25¼" (641 mm)
*The pipe distances listed in this table refer to the distances obtained when the
stove is installed in accordance with the appliance clearances above mentioned.
However, you can install the stove at reduced clearances; follow the instructions in
Section 7.4: Reducing Wall and Ceiling Clearances Safely. Where they are followed,
the new distance of the pipe to combustible materials must be respected in the
appropriate certification of the pipe.
USA
15" (381 mm)
17" (432 mm)
14" (356 mm)
48" (1220 mm)
76" (193 cm)
USA
18¾" (476 mm)
27" (686 mm)
25¼" (641 mm)
APPLIANCE CLEARANCES
(INSTALLATION WITH DOUBLE
WALL PIPE CONNECTOR)
CANADA
A
8" (203 mm)
B
17" (432 mm)
C
9" (229 mm)
K
48" (1220 mm)
L
76" (193 cm)
DISTANCES* FROM PIPE
CONNECTOR TO THE
COMBUSTIBLE MATERIALS
CANADA
D
11¾" (298 mm)
E
27" (686 mm)
F
20¼" (514 mm)
USA
8" (203 mm)
17" (432 mm)
9" (229 mm)
48" (1220 mm)
76" (193 cm)
USA
11¾" (298 mm)
27" (686 mm)
20¼" (514 mm)
31