Horizontal (Side Wall) Vent Termination:
To prevent blockage of the combustion air and exhaust vent
by snow, vent termination must be made 12" (in.) above the
anticipated maximum snow accumulation level (See Figure 1.9).
WARNING
Failure
to terminate
vent runs above the annual
snow accumulation
level may result in nuisance
furnace shutdown
and/or hazardous
condition
that
may lead to bodily harm or loss of life.
A minimum of 4' (ft.) clearance must be provided
from
electric meters, gas meters, regulators and relief equipment.
In
Canada refer to the current CAN/CGA B 149.1 and 2.
Direct vent (two pipe) terminations
must terminate
not
less that one-foot above, below or horizontal
from any inlet to
building.
Non-direct
vent (one pipe) termination
must terminate
at
least 4 feet below, 4 feet horizontally
from, or 1 foot above any
inlet to building.
Do not terminate over public walkways or over an area
where condensate or vapor could create a nuisance or hazard.
In
Canada refer to the current CAN/CGA B149.1 and 2.
Figure 1.9 HORIZONTAL VENT TERMINATION
HORIZONTAL
VENT TERMINATION
NOTE: T MIN. CLEARANCE
TO NEAREST BUILDING
OR WALL.
1.5" MIN.
18" MAX._
WALL
12 IN, ,VdN.
IHICKNESS --
_
12 IN. I_N.
i
l
I
J
i
t
i
i
_FLUE
Otm_ET
_
COJJPLING _"
""
....
_" MIN.
!
_AIR
INLET
m
TOP VIEW
SlOE VIEW
IH£
HORIZONTAL
OI_TANCE
IIETVCEEN
THE INTAKE
PIPE AND
EXHAUST
PIpE CAN
8E
INCRFJtSEO
IF N_RY
_
THE TERIdl NA'_ON
MUST
RI_dAIN
IN THE
PRESSURE ZONE.
;
,
i
i
i
i
J
MUST
HAVE
A 114' SLOPE
"_'JWAAO I_E FURNACE _R
VEto"
Condensate
Disposal Drain:
This furnace must use the condensate trap supplied with the
unit (See
Figure
2.9)
or
altemate
condensate
drain/trap
arrangement (See Figure 3.9) for proper drain installation.
The
ahemate arrangement should be used for uptTow installations when
the vent and condensate drain must be on opposite sides of the
furnace or for horizootal installation when space below the unit to
put the drain trap is at a minimum (order alternate condensate
drain/trap kit #20280001).
The drain must terminate at a floor
drain, sewer system, or drain vent for proper condensate removal.
Drain installation must conform to local building codes.
NOTE:
The condensate trap (supplied) must be connected to the
PVC tee provided on the unit. Failure to place the trap,
as per these instructions, may cause erratic unit operation
and nuisance furnace shutdown.
In addition the trap must be filled with water on the initial
start-up of the unit. installation location may require that the trap
be filled at the beginning of each heating season.
In addition, if this unit is placed in an unconditioned space
such,as an attic or crawlspace where the temperature could be at
freezing or below; a thermostatically
controlled beat tape must
be installed along the entire length of condensate drain in the
unconditioned space.
WARNING
Failure to install a heat tape on condensate drain
lines
in unconditioned
spaces
could
lead to
nuisance
furnace
shut-down,
water damage,
and/or a hazardous
condition
which may lead to
bodily harm, or loss of life.
Figure 2.9
STANDARD CONDENSATE TRAP
Figure 3.9
OPTIONAL
CONDENSATE
TRAP
FROM INDUCER A//D
VENT
PIPE
DRAIHS
TO
APPROVED
SEWER
SYSTEM
_FROM FURNACE
DRAIN
20246506
Issue 9939
Page 9 of 22