Blocked Vent ShutoffPressure
Switch Check:
To check the operation of the vent safety switch (PI), remove
the inlet pipe from the air inlet connector and remove the exhaust
vent from the induced draft motor vent coupling. Place the furnace
into operation.
Gradually cover up the air inlet; the main burners
should shut OFF.
Remove the restriction and the unit should
relight. Repeat the procedure, restricting the vent coupling outlet.
Replace the vent piping and reseal the opened joints as required.
Blocked
Drain
Safety
Pressure
Switch
Check:
The
blocked
drain
safety
switch
(P2)
has only
one
tube
connected
to it. To check the operation
of the blocked
drain safety
switch, place the unit into operation
and gradually
pinch the tube
closed.
The unit should
shut OFF.
Release
the restriction
on the
tubing and the unit should retight.
The operational
checkout
is now complete.
Be sure to adjust
the thermostat
to the desired
setting
and inform the homeowner
how to operate
the furnace system before leaving the job site.
SERVICING
THE FURNACE
CAUTION
Label
all wires
prior
to disconnection
when
servicing
controls,
Wiring
errors
can cause
improper and dangerous operation.
VER!FY
PROPER
OPERATION
AFTER
SERVICING.
WARNING
The ability to properly perform maintenance
on
this equipment
requires certain mechanical
skills
and tools. If you are at all uncertain, contact your
dealer for qualified
m_ntenance
and
service
since improper
service
Could lead to furnace
shutdown
or a hazardOUs condition
which could
lead to an unsafe condition and bodily harm.
7.
Reattach all wiring and piping as per the wiring diagram
and installation insmactions.
8.
Turn on utilities and check for leaks using soapy water and
a brush.
9.
A visual check of the main burner and pilot flame should be
made at the beginning of each heating season. See Figure
2.12 for proper pilot flame.
10. Check the input rate and adjust if necessary.
11. Perform a safety check of the limit control and blocked vent
shutoff switches and the blocked drain shut off switch.
12. Check the air filter, clean and/or replace as necessary.
13. Periodic cleaning of condensing coil and drain lines maybe
necessary for proper operation.
14. Replace the appropriate access panel or door.
Ne_er use
an 6pen flame
_hen
_fing
for g_
ie_i
Userf
_opea
fl_e
_oU!d [eadt6
: or explosi0n!
::
:::
certain
metalS.
Pipinl_
with :clean
water
after
leak
Combustion Component Check:
The heat exchanger, gas burners and venting system must
be checked each year, prior to the heating season, by a qualified
dealer/serviceman.
The following procedures should be performed:
1.
Remove appropriate access panel or door (see Figure 1.16).
2.
Remove the burner/manifold
assembly from the furnace,
following the instructions found on this page.
3.
Place the burner/manifold
assembly on a flat work area and
vacuum the burners.
It might be necessary to use a soft
bristly brush to remove dirt and then vacuum.
While
manifold assembly is out, check pilot location.
4.
Remove the burner opening inlet plate and the flue collector
box. This will expose both the burner and flue openings of
the primary heat exchangers.
5.
Vacuum the length of each heat exchanger tube using a
straight attachment into the burner openings and the flue
openings.
6.
Replace the flue collector box, burner opening inlet plate,
and burner/manifold
assembly.
Insure that all gaskets are
properly positioned and that no leaks exist.
Manifold (or Burner/Manifold)
Removal/Replacement:
1.
Make sure that all utilities (gas and electricity) are turned
off upstream of the furnace.
2.
Remove the louvered
access panel by sliding the panel
straight up, swinging the bottom of the panel away from the
furnace, and pulling the panel down and out of the furnace.
3.
Disconnect the gas line from the gas valve. Be sure that a
wiring diagram is available, or be ready to mark any wires
that are disconnected.
Unplug the four wire connector from
the gas valve.
20246506
Issue 9939
Page
15 of 22

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Ducane CMP A Series

Table of Contents