9-1. How to Set on PC Board

1. Turn off the power breaker to halt the supply of
electricity to the PC board.
2. Open the cover of the electrical box and confirm that
there is the indoor unit control PC board in it.
When using with high static pressure mode, set the
indoor unit control PC board as shown in Fig. 9-1.
3. Connect the short circuit connector to the short circuit
pin TP3 (2P: Yellow) of the indoor unit control board.
● In the case of wired remote control setting, do not
use the short circuit connector.
9-2. Operating the Timer Remote Controller
(CZ-RTC2)
9-2-1. How to set the external static pressure
1. Press and hold down the
simultaneously for 4 or more seconds.
(
, the Unit No., Item Code and Detailed Data
will blink on the LCD display.)
2. The indoor unit numbers in the group control will be
sequentially displayed whenever the Unit Select
button is pressed
Only the fan motor for the selected indoor unit will
operate during this time.
3. Specify the "
" item code by pressing the
/
buttons for the temperature setting
buttons and confirm the values.
("
" set at shipment )
4. Press the
/
buttons for the time to amend the
values for the set data.
Refer to Table 9-2 and Fig. 9-2 and select a value
"
".
5. Press the
button.
The display will stop blinking and remain illuminated.
6. Press the
button. The fan motor will stop
operating and the LCD display will return to the
normal stop mode.
,
and
buttons
.
Table 9-1 External static pressure
Type
Standard
High static pressure
IC001
Table 9-2 Setting the external static pressure
Indoor unit
7
9
12
External static pressure of the rated air flow
volume
0.04
0.06
10
15
0.12
0.12
30
30
1
5
6
NOTE:
Failure to set this parameter may result in decreased airflow and
condensation.
21
7
9
12
in.WC
0.04
0.06
0.06
Pa
10
15
15
in.WC
0.12
0.12
0.16
Pa
30
30
40
White Yellow Red
TP6
TP3
IC010
FAN-TAP
TP6 TP3
TP1
CN041
CN044
CN040
RC
EMG
OC
15
18
0.06
in.WC
15
Pa
0.16
in.WC
40
Pa
1
4
CZ-RTC2
15
18
0.06
0.06
15
15
0.16
0.16
40
40
T5A L250V
TP1
Fig. 9-1
Item code
2
3