CS-F50DTE5 CU-L50DBE8
10.2. Refrigerant additional charge
1. Piping installation by standard piping
• • • • At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30 m.
(Refer the following table)
But when the piping length exceeds 30m, additional charge is required according to the following table.
Example:
CU-L50DBE8
In case of 50m long pipe (one way), the amount of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g
Attention
• • • • Do not decrease the size of the gas piping. (It causes the breakdown of the compressor)
10.3. Position of the centre gravity
MODEL NAME
WIDTH (mm)
CU-L34DBE5
CU-L43DBE5
CU-L50DBE8
Model Name
Liquid piping
(dia.mm)
CU-L34DBE5
9.53
CU-L43DBE5
9.53
CU-L50DBE8
9.53
OUTSIDE DIMENSIONS
DEPTH (mm)
900
320
900
320
900
320
Standard piping specification
Gas piping
Gas charge-
(dia.mm)
less length
(m)
15.88
30
15.88
30
15.88
30
NET WEIGHT
HEIGHT (mm)
kg
1340
110
1340
110
1340
110
34
Additional
gas volume
(g/m)
50
50
50
CENTRE OF GRAVITY
X (mm)
Y (mm)
720
160
720
160
720
160
Z (mm)
460
460
460