Wiring Configuration: Advanced Models (HE150/HE250/HE300)
Wiring to force the HVAC system fan on whenever humidity is needed (on demand).
HE150 OR HE250
G (THERMOSTAT)
R
G (FURNACE)
1
ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G.
IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION
AND ROUTE THROUGH HUMIDIFIER AS SHOWN.
2
HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN.
HE100/HE200 USES A 10 VA TRANSFORMER WIRED INTO 24V IN.
Wiring to force fan on and prove airflow in the duct.
HE150 OR HE250
G (THERMOSTAT)
R
HUMIDITY
CONTROL
G (FURNACE)
ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G.
1
IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION
AND ROUTE THROUGH HUMIDIFIER AS SHOWN.
HE150/HE250 USES A 15 VA TRANSFORMER WIRED INTO 24V IN.
2
HE100/HE200 USES A 10 VA TRANSFORMER WIRED INTO 24V IN.
18
POWER OUT
24V FOR
1
ELECTRONIC
HUMIDISTAT
FROM
HUMIDITY
2
CONTROL
POWER IN
POWER OUT
24V FOR
1
ELECTRONIC
HUMIDISTAT
AFS
FROM
2
POWER IN
G (FURNACE)
2
POWER IN
DIP SWITCH SETTING
RESET POWER AFTER
ANY DIP SWITCH CHANGES
G (FURNACE)
2
POWER IN
DIP SWITCH SETTING
RESET POWER AFTER
ANY DIP SWITCH CHANGES
HE300
POWER OUT
G (THERMOSTAT)
24V FOR
1
ELECTRONIC
HUMIDISTAT
FROM
R
HUMIDITY
CONTROL
1
ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G.
IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION
AND ROUTE THROUGH HUMIDIFIER AS SHOWN.
2
HE300 USES A LINE CORD PLUG.
HE300
POWER OUT
G (THERMOSTAT)
24V FOR
1
ELECTRONIC
HUMIDISTAT
FROM
R
HUMIDITY
CONTROL
ONLY NEEDED IF SYSTEM'S THERMOSTAT DOES NOT ISOLATE Y FROM G.
1
IF NEEDED, BREAK THE THERMOSTAT G TO SYSTEM G CONNECTION
AND ROUTE THROUGH HUMIDIFIER AS SHOWN.
HE300 USES A LINE CORD PLUG.
2
Humidifier 69-2413EF—05
M29940A
AFS
M29941A