5.2.3.1
Vertical collector position
Conditions: Number of collectors: 4 ... 6, Connected on opposite sides
1
Insert the flow (outlet) (1) on one side in the upper lat-
eral opening and insert the return (inlet) (2) diagonally
opposite this in the lower lateral opening.
Secure the connections with the clamps.
1
Install the plugs (1) at the bottom of the collector.
Install the plugs (2) at the top of the collector.
Secure the plugs with the clamps.
Connect the collector flow and return to the system with
the connection tubes.
Check the connections for tightness.
Select the opening in the collector field that is nearest to
the flow connection.
On the selected collector, use a screwdriver (1) to push
the rubber stopper for the temperature sensor through to
the marking.
Do not remove the rubber stopper.
Push the temperature sensor through the rubber stopper
until you can feel significant resistance (2).
0020159946_01 auroTHERM classic Installation manual
Flat roof fitting and installation 5
2
2
1
2
33