Mitsubishi Electric PLA-RP-AA Technical Data Book page 13

Heat pump air conditioners
Hide thumbs Also See for PLA-RP-AA:
Table of Contents

Advertisement

Model name
Cooling
Heating
Power supply
Indoor unit
Outdoor unit
Refrigerant pipe size
Refrigerant pipe length
NOTE:
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
Upper limit D.B. 28˚C
Heating
Lower limit D.B. 17˚C
Indoor unit
Outdoor unit
Capacity
Total input
EER
SRI
SHF
Capacity
Total input
COP
SRI
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Gas side O.D.
Liquid side O.D.
Height difference
Length
Indoor
D.B. -5˚C
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C
PEA-RP71EA
PUHZ-RP71VHA
Btu/h
24,200
kW
7.1(3.3-8.1)
kW
2.48
2.86
3.87
0.82
Btu/h
27,300
kW
8.0(3.5-10.2)
kW
2.47
3.24
4.13
kW
[
Hz
50
V
230
A
25
CMM
22-27
CFM
780-955
Pa
125
dB(A)
52-55
Galvanized sheets
W : mm
785
D : mm
690
H : mm
428
W : inch
31
D : inch
27-1/16
H : inch
16-7/8
kg
46
lbs
101
R1(External thread)
CMM
55
CFM
1,940
dB(A)
47
dB(A)
48
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
kg
75
lbs
165
mm
15.88
inch
5/8
mm
9.52
inch
3/8
m
Max. 30
m
Max. 50
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F)
W.B. 6: (43˚F)
3. Guaranteed voltage
198~264V, 50Hz
Outdoor
4. Above data based on indicated voltage
w
Indoor unit
Outdoor unit
w
If optional Air protect guide installed. D.B.-15:
13
-
1
Single phase 230V 50Hz
Single phase 230V 50Hz

Advertisement