Dunkirk 95M-200 Parameter Manual page 13

Gas-fired direct vent modulating hot water boiler
Table of Contents

Advertisement

Para.
Name
T4 Frost
8
-22° to 50°F
Protection
9
T4 Correction
-8° to 10°F
10
T Blocking
34° - 140°F
(no booster)
11
Booster Time
T Parallel
12
0 to 144°F
Shift
2250 to 5200
Maximum fan
13
speed CH
2400 to 5200
2250 to 5200
Maximum fan
15
speed DHW
2400 to 5200
Range
Gascom
Boiler
Software
Display
-22 to 50
-8 to10
32° (off)
32 (off)
34 - 140
0
0 to 30
1 to 30
(minutes)
0 to 144
NAT
22 to 52 (100's
of rpm)
LP
24 to 52
(100's of rpm)
NAT
22 to 52 (100's
of rpm)
LP
24 to 52
(100's of rpm)
Boiler Display
Display Position
1st
2nd
3rd
4th
Initial reading:
P
.
0
After 2 to 3 seconds:
Blank
Setting
Initial reading:
P
.
0
After 2 to 3 seconds:
Blank
Blank
Setting
Initial reading:
P
.
1
After 2 to 3 seconds:
Blank
Setting
Initial reading:
P
.
1
After 2 to 3 seconds:
Blank
Blank
Setting
Initial reading:
P
.
1
After 2 to 3 seconds:
Blank
Setting
Initial reading:
P
.
1
After 2 to 3 seconds:
Blank
Setting
Initial reading:
P
.
1
After 2 to 3 seconds:
Blank
Blank
Setting
13
Description
When outside temperature drops to this
8
number, the boiler circulator will run con-
stantly.
Use this parameter to modify the outside
9
temperature reading if needed to correct
for outside sensor location. Use only if sen-
sor is providing a false reading.
When the target outlet water temperature
0
is less than this setting, the boiler shuts
off.
• If a call for heat causes the boiler to re-
main at high fire for a time equal to Param-
1
eter 11, the control module increases out-
let water temperature setpoint by 18°F. For
each additional Parameter 11 time the heat
call continues, the set point is increased
another 18°F (never exceeding Parameter
4 + Parameter 23 (hysteresis off))
• To deactivate booster operation, set this
parameter to 0.
• The value of Parameter 12 reduces the
calculated setpoint temperature by the
amount set when the call for heat is from
2
outdoor temperature.
• We recommend not changing this param-
eter from the factory default of 0 (no paral-
lel shift).
• Use this parameter to change the maxi-
mum boiler input for central heating (CH).
Never above default value .
• When in central heating mode, the boiler
fan speed will not exceed this setting. In-
3
creasing fan speed increases boiler input;
decreasing fan speed decreases boiler in-
put.
• Never set below low fire setting or above
maximum value shown at left.
• Use this parameter to change the maxi-
mum boiler input for domestic water heat-
ing (DHW)-NEVER above default value.
5
• Boiler fan speed will not exceed this set-
ting in DHW mode. Increasing fan speed in-
creases boiler input; decreasing fan speed
increases fan speed decreases input.
•NEVER set below low fire setting or above
the maximum value shown at left.