(a) Inspection of electronic expansion valve
Electronic expansion valve operates for approx. 10 seconds after the power on, in order to determine its aperture. Check the
operating sound and voltage during the period of time. (Voltage cannot be checked during operation in which only the aperture
change occurs.)
(i) If it is heard the sound of operating electronic expansion valve, it is almost normal.
(ii) If the operating sound is not heard, check the output voltage.
Expansion valve connector
(6P, black)
(iii) If voltage is detected, the outdoor PCB is normal.
(iv) If the expansion valve does not operate (no operating sound) while voltage is detected, the expansion valve is defective.
• Inspection of electronic expansion valve as a separate unit
Measure the resistance between terminals with an analog tester.
Measuring point
Resistance when normal
1 – 6
1 – 4
1 – 3
1 – 5
(b) Outdoor unit fan motor check procedure
• When the outdoor unit fan motor error is detected, diagnose which of the outdoor unit fan motor or outdoor PCB is defective.
• Diagnose this only after confirming that the indoor unit is normal.
(i)
Outdoor PCB output check
1)
Turn off the power.
2)
Disconnect the outdoor unit fan motor connector CNFAN.
3)
When the indoor unit is operated by inserting the power supply plug and pressing (ON) the backup switch for more
than 5 seconds, if the voltage of pin No. ② in the following figure is output for 30 seconds at 20 seconds after
turning "ON" the backup switch, the outdoor PCB is normal but the fan motor is defective.
If the voltage is not detected, the outdoor PCB is defective but the fan motor is normal.
Note (1) The voltage is output 3 times repeatedly. If it is not detected, the indoor unit displays the error message.
CNFAN
DC308~336V
(ii) Fan motor resistance check
Measuring point
⑥ - ④ (Red - Black)
③ - ④ (White - Black)
6
5
4
3
2
1
46 ± 4Ω
(at 20ºC)
FM
0
GND
DC15V
(−)
Resistance when normal
20 MΩ or higher
20 kΩ or higher
1
- 3
1
- 4
Approx. DC5 V is detected for 10 seconds after the power on.
1
- 5
1
- 6
Outdoor PCB
DC several (4~7V)
Notes (1) Remove the fan motor and measure it without power connected to it.
Notes
(2) If the measured value is below the value when the motor is normal, it means that
the fan motor is faulty.
59
-
-
'13 • SRK-T-140
Measuring
Resistance when
point
normal
⑥ - ④
DC 308~336V
③ - ④
DC 15V
② - ④
DC several V (4~7V)
① - ④
DC several V (4~7V)