Daikin FTXS60GV1B Installation Manual page 11

Hide thumbs Also See for FTXS60GV1B:
Table of Contents

Advertisement

Indoor Unit Installation
4.
Laying piping, hoses, and wiring
4-1. Right-side, right-back, or right-bottom
piping
1) Attach the drain hose to the underside of the
refrigerant pipes with adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together
with insulation tape.
3) Pass the drain hose and refrigerant pipes through the
wall hole, then set the indoor unit on the mounting
plate hooks by using the
indoor unit as a guide.
4-2. Left-side, left-back, or left-bottom piping
1) Replace the drain plug and drain hose.
2) Attach the drain hose to the underside of the
refrigerant pipes with adhesive vinyl tape.
3) Be sure to connect the drain hose to the drain port in
place of a drain plug.
4) Shape the refrigerant pipe along the pipe path
marking on the mounting plate.
5) Pass drain hose and refrigerant pipes through
the wall hole, then set the indoor unit on
mounting plate hooks, using the
the top of indoor unit as a guide.
6) Pull in the inter-unit wiring.
7) Connect the inter-unit piping.
8) Wrap the refrigerant pipes and drain hose together with insulation tape as
right figure, in case of setting the drain hose through the back of the
indoor unit.
9) While exercising care so that the inter-unit wiring do not catch indoor unit,
press the bottom edge of indoor unit with both hands until it is firmly
caught by the mounting plate hooks. Secure indoor unit to the mounting
plate with indoor unit fixing screws (M4 × 12L).
4-3. Wall embedded piping
Follow the instructions given under left-side, left-back, or left-
bottom piping.
Insert the drain hose to this depth so it won't be pulled out of
the drain pipe.
9
markings at the top of the
markings at
Caulk this hole
with putty or
caulking material.
Remove pipe port cover
here for right-side piping
Remove pipe port cover
here for right-bottom piping
Right-bottom
piping
Remove pipe port cover here for left-bottom piping
How to set drain plug
Insert a hexagonal wrench (4mm).
Drain hose
Bind with plastic
tape.
Insert the drain hose to this depth so
it won't be pulled out of drain pipe.
Right-back piping
Bind coolant pipe and drain hose
together with insulating tape.
A
Mounting plate
Remove pipe port cover
here for left-side piping
Left-side piping
Left-back piping
Left-bottom piping
Do not apply lubricating oil (refrigeration oil)
when inserting.
Application of causes deterioration and drain
leakage of the plug.
A
Mounting plate
Wrap insulating tape around the bent portion
of refrigerant pipe.
Overlap at least half the width of the tape
with each turn.
A
Mounting
Drain hose
plate
Bottom frame
F Indoor unit fixing screw
(M4 × 12L) (2 point)
Inner wall
50mm
Drain hose
or more
Vinyl chloride drain pipe
(VP-30)
Outer wall
■English
Refrigerant
pipes