Installation and Service Instructions AUTOMATIC 11.15am 71°F Boiler Controls For the installing contractor Logamatic 2107 Please read carefully prior to commissioning or ser- vicing.
Page 2
Change to SETBACK if no room sensor is being used or RMSETBACK if a room sensor is present Refer to page 10 for additional details. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
The pan must not restrict combustion air flow. CAUTION: Personal injury and property damage. Appliance must be installed vertically. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
RISK TO LIFE z In an emergency, switch OFF the emergency shutoff switch outside the WARNING! boiler room. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
MAX TEMP Maximum heating circuit temperature REMOTE 2 Remote control ON/OFF DIFF T Room temperature hook-up OA SETBACK Type of setback OFFSET Room temperature offset Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 8
6 Only if FM 241 module is installed and if heating circuit 2 is selected as an "UND-FLOOR" or "RADIATOR" heating system. 7 Only if FM 244 module is installed. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
G234: The tridicator assembly should be moved to the supply piping and replaced with the chrome plated Logamatic well. The sensor bundle must be inserted into this well. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 10
Tilt the display to the desired position. z Replace the top housing of the controls and fasten the two screws. The control is ready to be placed into operation. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Item 5: ON/OFF switch Item 6: Keys for basic functions Item 7: Dial Item 8: Keys for extended functions Item 9: Display Item 10: Flap Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 12
Item 1: Automatic mode following a program Item 2: Normal heating mode (day mode) Item 3: Flue gas test (for measuring flue gases) Item 4: Setback heating mode (night mode) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 13
"Display" key – Select the standard display This keypad is used, for example, to enter the day, set the time, select temperature values, etc. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Hold down the "Display" key and turn the dial, until "BURNER ON" appears in the display. The burner starts running. BURNER Release the "Display" key. °F Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 15
(Fig. 6). 1...7 Zeit Temp PROG Urlaub Auswahl So/Wi Anzeige Install Zurück Fig. 6 Remove the STB cover. Item 1: STB cover. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
The service level is now activated. USER NOTE The unit automatically returns to the standard display if no settings are made within 5 minutes. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
REMOTE Press the "ENTER" key to return to the higher-level menu. CIRCUIT 1 PERIM HTG Press the "AUT" key to exit the service level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Return to the standard display Press "ENTER". The unit automatically returns to the standard display if no key is pressed within 5 minutes. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
5 second pause, then the mixing valves are set to "OPEN" for 3 minutes. All pumps then return to normal operation. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
The setting applies to all heating circuits. Input range Factory setting System frost protection -4°F – 50°F (-20°C – 10°C) 41°F (5°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Note: In areas where rapid changes in outdoor temperature occur, choose Building Response 1. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 22
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting 1 (low) Building response 2 (medium) 3 (high) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Press "ENTER" to return to the next higher level. Input range Factory setting Burner system without burner module FM 242 – 1-stage 1-stage/2-stage/modulating 2-stage Burner system with burner module FM 242 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting 10 %–60 % 30 % minimum modulation output Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Press "ENTER" to return to the next higher level. Input range Factory setting Operating time of the actuator 5 – 60 seconds 12 seconds Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Press "ENTER" to return to the next higher level. Input range Factory setting Pump logic for 104°F (40°C) 1-stage 60°F – 140°F 113°F (45°C) 2-stage (15°C – 60°C) 122°F (50°C) Modulating burners Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Input range Factory setting 158°F – 210°F Maximum OFF temperature 176°F (80°C) (70°C – 99°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
"AMERICAN". Now hold down the "Display" key and turn the dial to set the language. Release the "Display" key to store the set language. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
If the right heating system is selected, the other heating circuit parameters are preset. They must still be verified, however. Further information on this can be found on the next page. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 30
If there is only one heating circuit with mixing valve present (HK2), circuit 1 must be set to "NO SYSTEM". If the "NO SYSTEM" setting is used, all of the following settings are hidden for this circuit. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 31
FLOOR HTG Input range Factory setting NO SYSTEM Heating circuit 1 PERIM HTG PERIM HTG NO SYSTEM Heating circuit 2 FLOOR HTG FLOOR HTG Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
(+20) (+15) (+10) (+5) (±0) (-5) (-10) (-15) The factory setting is: Outdoor temperature [°F(°C)] With PERIM HTG: 167°F (75°C) Fig. 9 Determining the heating With FLOOR HTG: 113°F (45°C) curve Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 33
Reference design temperature for PERIM HTG 86 – 194°F (30 – 90°C) 167°F (75°C) Reference design temperature for FLOOR HTG 86 – 140°F (30 – 60°C) 113°F (45°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
(in this case "OFF"). DHW PRIOR Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting DHW priority Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
68 – 140°F (20°C – 60°C) 122°F (50°C) FLOOR HTG* * This function does not replace the safety thermostat for switching of the pump for radiant heating circuit. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Further information on this can be found on the next page. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 37
"REMOTE" appears on the display if the remote control is active. All settings can then only be made via the remote control. Input range Factory setting Remote control Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
This setting is generally recommended for FLOOR HTG systems. The factory setting is: With FLOOR HTG system: 6°F (3°C) Further information on this can be found on the next page. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 39
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting Differential temperature 6°F (3°C) 2 – 18°F (1°C – 10°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Heating circuit with constant circulation zone: RMSETBACK (Requires room sensor) Heating circuit with ONlOFF thermostats: SETBACK (No room sensor present) Commercial (day use only) buildings: OASETBACK Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 41
Press "ENTER" to return to the next higher level. Input range Factory setting Outdoor setback Room setback Type of setback Outdoor setback Setback Boiler off Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting OFFSET -9 – +9°F (-5°C – +5°C) 0°F (0°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
(in this case "SLRFN OFF"). SLRFN OFF Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting SOLAR Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
"MAX-SL SR" setting in order to prevent the tank scaling up. Input range Factory setting Max sol T 140 – 194°F (60°C – 90°C) 167°F (75°C) Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting 86 – 130°F (30°C – 54°C) MIN SL SR Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
(in this case "OFF"). DHW PROD Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting DHW production Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
The intermittent mode may be set to 1 to 6 pump starts per hour in order to minimize the operating costs of the recirculation pump. This setting saves energy while ensuring comfort. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 48
(in this case "4"). RECIRCPUMP Release "Display" to store your input. Press "ENTER" to return to the next higher level. Input range Factory setting DHW recirculation pump Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
50°F (+10°C), the second at 32°F (±0°C) and the third at 14°F (-10°C). HTG CURVE °F HTG CURVE °F HTG CURVE °F Release the "Display" key to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Boiler system pump HK1 z Heating circuit pump HK 2 z Mix valve open/closed/OFF z Tank DHW pump z DHW recirculation pump z Solar pump Logamatic 2107 controls - We reserve the righ to make any change due to technical modifications.
Page 51
Press "ENTER" to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Hold down "Display" and turn the dial. All the numbers and symbols must appear on the display. °F°C Release the "Display" key. 1234567 Press "ENTER" to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Release "ENTER" to store your input. Press the "Display" key to return to the next higher level. Input range Factory setting -30 seconds/day – +30 seconds/day Time Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
No "RESET" is carried out if you release the "Display" key before all the num- bers have disappeared. Press "ENTER" to return to the next higher level. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
"AMERICAN" appears as the first main menu. Turn the dial until "VERSION" and the version number (in this case "3.24") are displayed. VERSION 3.24 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
5 5 5 0 0 0 (1 1 1 0 0 0 ) 6 6 6 0 0 0 (1 1 1 5 5 5 ) (- ) Outdoor temperature [°F (°C)] Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 57
Water temperature [°F (°C)] Collector sensor (FSK) -58 (-50) 32 (0) 122 (50) 212 (100) 302 (150) 392 (200) 482 (250) Collector temperature [°F (°C)] Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Outdoor setback Room setback Setback type for heating circuit 2 Outdoor setback Setback Switch-off Further information on this can be found on the next page. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 59
167°F (75°C) MIN-SL SR 86 – 130°F (30°C – 54°C)/OFF DHW PROD ON/OFF DHW recirculation pump OFF/1/2/3/4/5/6/ON Time -30 seconds/day – +30 seconds/day 0 seconds/day Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Check the wiring Remote control is defective available, so the ambient REMOTE2 ERROR Replace the remote control influence does not apply Connecting cable interrupted Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 61
Module no longer present Module is no longer being (solar card) Plug the module in again Module defective addressed Replace the module FM 244 ERROR Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
The differential is split above & below the current target temperature. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 63
11 to Hot on the burner (terminal 4 is the the burner is now low voltage between terminals 10 & 11 neutral). on the R2107 and TT (or RW) on the boiler aquastat. Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 64
Troubleshooting Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
With this type of a call, you will want to increase the OFFSET setting. USE THE QUICK REFERNECE GUIDE FOR INITIAL PROGRAMMING Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Check the following: 1 - bad circulator 2 - stuck flow check 3 - piping is air bound 4 - closed valve Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Type of setback ....4 0 Version number ....5 5 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 70
Notes Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 71
Notes Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Page 72
U U U n n n i i i t t t e e e d d d S S S t t t a a a t t t e e e s s s a a a n n n d d d C C C a a a n n n a a a d d d a a a Bosch Thermotechnology Corp. 50 Wentworth Avenue Londonderry, NH 03053 Tel. 603-552-1100 Fax 603-965-7581 www.buderus.us U.S.A. Products manufactured by Bosch Thermotechnik GmbH Sophienstrasse 30-32 D-35576 Wetzlar www.buderus.com...
Need help?
Do you have a question about the Logamatic 2107 and is the answer not in the manual?
Questions and answers
Почему в ночном режиме не греется горячая вода