Yunca Gas hobson Installation Instructions

Freestanding

Advertisement

Quick Links

HOBSON FREESTANDING WOODBURNER
A. Yunca recommends that competent trades persons carry out all installations (e.g. AHHA
Registered Installer), to obtain maximum performance and safe, efficient heating.
B. A permit is required and we suggest you check with local building inspectors as by-laws do
vary from area to area.
Also notify your Insurance Company that a solid fuel heater has been installed.
C. Floor Protector –
1. Must extend a minimum of 300mm in front of the door aperture.
2. Must extend at least 100mm from each side panel of the heater.
3. Ash Floor Protector must be constructed of non-combustible materials.
D. Seismic restraint – Heater must be restrained from seismic movement as required by
AS/NZS 2918:2001. 10mm diameter bolting holes in the feet of the HOBSON allow restraint.
E. Manufacturers' recommended tested minimum clearances from combustible walls:
Tested to AS/NZS 2918 : 2012 by VIPAC ENGINEERS & SCIENTISTS
Rear Clearance (with YUNCA flue mounted shield fitted)
Side Clearance (with YUNCA flue mounted shield fitted)
Corner Clearance (with YUNCA flue mounted shield fitted)
Tested to AS/NZS 2918 : 2012 by VIPAC ENGINEERS & SCIENTISTS
Rear Clearance (with AUSTRALIAN flue mounted shield fitted – The Flue Factory)
Side Clearance (with AUSTRALIAN flue mounted shield fitted – The Flue Factory)
Corner Clearance (with AUSTRALIAN flue mounted shield fitted – The Flue Factory)
F. Standard 150mm Flue Kit (Tested to AS/NZS 2918:2001 Appendix F): FIG A, B & E
1. 4.2m x 150mm stainless steel flue
2. 2.4m x 250mm galvanised liner.
3. Ceiling Plate.
Please Note: All flue joints must be sealed with flue sealing compound. Use stainless steel screws or
rivets to join the flue pipe (three equally spaced places at each joint).
be fixed to the flue spigot with at least one stainless steel screw or rivet.
flue termination height is 4.6 m above the floor protector.
G. HOBSON Yunca Flue Mounted Shield (Flue Guard) Kit.
Complies (with heater) to AS/NZS 2918:2001): Refer FIG A
1 x 1200mm length lined back guard.
1 x 1200mm length perforated front guard
1 x 1200mm length tertiary back guard with spacer tabs.
1 x Top front deflector shield (half round shape, this is angled 30 degrees when installed).
H. AUSTRALIAN (Flue Factory Flue Mounted Shield (Flue Guard) Kit.
Standard Triple lined flue guard kit.
Please Note: The minimum Flue Mounted Shield height is 1200mm.
HOBSON – TYPICAL INSTALLATION (Drawings not to scale)
Hobson Installation AUSTRALIA - AUG 2014.doc
A division of Terry Young Ltd, New Zealand
INSTALLATION INSTRUCTIONS for
AUSTRALIA - AUGUST 2014
TESTED in compliance with AS/NZS 2918: 2001
HARDWOOD TEST No. 30A-12-0038-TRP-254693-1
3. 1 x insulation boundary shield.
4. 2 x spider brackets.
6. 1 x weather cap & cowl.
www.yunca.co.nz
Clearance
150 mm
330 mm
90mm
Clearance
200 mm
330 mm
140 mm
The first length of flue must
The required minimum
Page 1 of 4

Advertisement

loading

Summary of Contents for Yunca Gas hobson

  • Page 1 3. Ash Floor Protector must be constructed of non-combustible materials. D. Seismic restraint – Heater must be restrained from seismic movement as required by AS/NZS 2918:2001. 10mm diameter bolting holes in the feet of the HOBSON allow restraint. E. Manufacturers’ recommended tested minimum clearances from combustible walls: Tested to AS/NZS 2918 : 2012 by VIPAC ENGINEERS &...
  • Page 2 FIG A (below, left): HOBSON (Sub 1.0) Flue Mounted Shield (Flue Guard) Kit. Complies (with heater) to AS/NZS 2918:2001 TOP CAP (Fits inside flue) ENLARGEMENT OF CEI LI NG ASSEMBLY FIG B 2 5 m m m in . BETWEEN LI NER & ANY TI MBER...
  • Page 3 Ash Floor Protector FIG D: HEATER POSITION:- N.B. The “B” and “D” measurements on the Hobson are taken from the heater sides. “O” measurement is the width of the heater, excluding the cook top surface. Above: Non combustible wall clearances. Brick lining from floor to within 25mm of ceiling.
  • Page 4: Important Information

    INSTALLATION UNSAFE. IF A WATERBOOSTER IS FITTED: NOTE: A WATER BOOSTER CANNOT BE FITTED TO THE HOBSON (SUB 1.0) CLEAN AIR MODEL A. DO NOT CONNECT TO AN UNVENTED HOT WATER SYSTEM B. INSTALL IN ACCORDANCE WITH AS 3500.4.1 OR NZS 4603 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODES.