Commissioning; To Fill And Turn On The Water Heater; Gas Inlet Pressure - Rheem Stellar 850330 Owner's Manual And Installation Instructions

850 series gas domestic outdoor water heater
Table of Contents

Advertisement

TO FILL AND TURN ON THE WATER HEATER

The gas pilot or burner must not be lit until the water heater is filled with
water.
Open all of the hot water taps in the house (don't forget the shower).
Open the cold water isolation valve fully to the water heater.
Air will be forced out of the taps.
Close each tap as water flows freely from it.
Check the pipe work for leaks.
Open the gas isolation valve fully.
Check the gas pipe work for leaks.
Light the water heater (refer to
Warning: Upon completion of the installation and commissioning of the
water heater, leave this guide with the householder or responsible officer.
DO NOT leave this guide inside of the cover of the water heater, as it may
interfere with the safe operation of the water heater or ignite when the water
heater is turned on.
Explain to the householder or a responsible officer the functions and operation
of the water heater.

GAS INLET PRESSURE

IMPORTANT – CHECK the gas supply pressure at the inlet to the water heater
with the water heater and all other gas burning appliances in the premises
operating (burners alight). The minimum gas supply pressure is:
Natural Gas
Universal LPG
If this minimum cannot be achieved, it may indicate the meter or the gas line to
the water heater is undersized. It is important to ensure that an adequate gas
supply pressure is available to the water heater when other gas burning
appliances, on the same gas supply, are operating.

COMMISSIONING

"Lighting the Water Heater"
1.13 kPa
2.75 kPa
34
on page 36).
Propane
2.75 kPa
Butane
2.75 kPa