Toshiba RAS-24UAH-E-1 Service Manual page 72

Table of Contents

Advertisement

No.
Procedure
5
Press [START/STOP] button once
to start the unit.
• Shorten the time of the restart
delay timer.
• Set the operation mode to COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature much
lower than the room temperature.
(The unit (compressor) operates
continuously in the above
condition.)
6
If the above condition (No. 6) still
continues, start the unit in the
following condition.
• Set the operation mode to HEAT.
• Set the preset temperature much
higher than room temperature.
7
Connect the motor connector to the
motor and turn on the power supply.
Start the unit in the following
condition.
• Set the operation mode to FAN.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above codition.)
Temperature
Resistance value
9-8-2. How to Shorten Time of Restart Delay Timer
1 Press [CLR] button while pressing [CHECK] button
with a tip of a pencil.
2 Then press [START/STOP] button to transmit the
signal to the indoor unit.
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION lamp blinks.
1. Check it is impossible to detect the
voltage (DC 15 V) between 3 and
4 of the motor terminals.
2. The motor does not operate.
(But it is possible to receive the
signal from the remote control.)
3. The motor rotates but vibrates
strongly.
Table 9-8-2 Approximate resistance value of thermo sensor
0°C
10°C
33.8
20.35
Check points
20°C
12.59
AUTOA
FAN
SWING
FIX
ON
– 71 –
FILE NO. SVM-03010(1)
Causes
1. The temperature of the indoor
heat exchanger is extremely low.
2. The connection of the heat
exchanger sensor is loose.
(The connector is disconnected.)
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 9-8-2.)
4. The main P.C. board is defective.
1. The temperature of the indoor
heat exchanger is extremely high.
2. The connector of the heat
exchanger sensor short-circuited.
(CN01)
3. The heat exchanger sensor and
the P.C. board are defective. (Refer
to Table 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective.
(Protected operation of P.C. board)
2. The connection of the motor
connector is loose.
3. The P.C. board is defective.
25°C
30°C
10.0
7.99
A
B
PRESET
2
START/STOP
AUTO
MODE
ECO
Hi-POWER
TIMER
MEMO
17 1
OFF
SET
CLR
FILTER
RESET
CLOCK CHECK
(kΩ)