System air conditioner
Hide thumbs Also See for EH035CAV:
Table of Contents

Advertisement

Alignment and Adjustments
Operating Instructions and Installation
3-1-1 Wired Remocon Error Display (COM2)
Display
3-3
141 Kinderkamack Rd, Park Ridge, NJ 07656 Tel: 201-782-1782 Fax: 201-782-1783 Web: www.amgair.com Email: info@amgair.com
Explanation
Indoor unit Communication Error
Indoor/Outdoor unit Communication Time Out Error
60 Packet Over data
Indoor unit is not connected
Communication Error between Outdoor Main and Inverter Micom
(Occurred after I minute detection in Main and Inverter)
Indoor Temp. Sensor(OPEN/SHORT ERROR)
Indoor Unit Eva in sensor(OPEN/SHORT ERROR)
Indoor Unit Eva in sensor Separation
Outdoor Temp. Sensor Error(OPEN/SHORT ERROR)
COND Temp. Sensor Error(OPEN/SHORT ERROR)
Inverter Compressor Discharge Temp. sensor Error(OPEN/SHORT ERROR)
Indoor Float S/W 2
nd
Detection
Outdoor unit-Indoor unit Communication wire Voltage Detection
Outdoor unit Refrigerant Full Leakage(Gas Leak)
Outdoor door Fan Error
[Inverter]Inverter Comp. Start Failure
[Inverter]DC PEAK Error
[Inverter]DC LINK Voltage 150V below, 410V Over
[Inverter]Comp. Rotation Error
[Inverter]Current Sensor Error
[Inverter]DC LINK Sensor Error
[Inverter]EEPROM READ/WRITE Error
[Inverter]Inverter ZEROCROSSING Error
Outdoor unit Capacity Setup Option Error
Wired Liquid Crystal Indoor unit Comm. Error
Master Wired Liquid Crystal Slave Liquid Crystal Comm. Error
Wired Liquid Crystal COM1/COM2 Cross Error
Error of setting option for wired remote controller COM2
Air Marketing Group LLC
Follow-up Measures
Refer to
troubleshooting(12-2-12)
Indoor Sensor Error
(Use same measures as Outdoor
Sensor Error, troubleshooting 12-2-6)
Outdoor Sensor Error
(Refer to troubleshooting 12-2-6)
Refer to
troubleshooting(12-2-12)
Recharge Gas
Refer to
troubleshooting(12-2-3, 12-2-9)
Refer to
troubleshooting(12-2-13)
Refer to
troubleshooting(12-2-11)
Refer to
troubleshooting(12-2-15)
Exchange PCB  Exchange Comp
Exchange PCB
Refer to troubleshooting(12-2-10)
Exchange Outdoor PCB
Exchange Outdoor PCB
Reset Option Code
System Multi A/C
Self Diagnosis
Samsung Electronics