YES
Are all of compressor cords normal?
YES
Is compressor motor winding normal?
(Check winding resistor.)
YES
Is capacitor for compressor normal?
YES
Is overload relay normal?
YES
Does compressor start?
YES
Does compressor stop after a while?
YES
Is gas quantity normal?
(Check gas pressure.)
YES
Compressor is defective.
YES
Replace compressor.
NO
NO
Compressor is defective.
NO
Capacitor is defective.
NO
Overload relay is defective.
NO
Compressor is defective.
NO
Gas shortage (Gas leak)
– 61 –
FILE NO. SVM-04007
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.