Desa VN18B Safety Information And Installation Manual page 13

Unvented (vent-free) infrared gas heater
Table of Contents

Advertisement

INSTALLATION
Continued
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply a noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Test Pressures Equal To or Less Than 1/2
PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 16).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter for natural
gas (see Figure 17) or propane/LP supply
tank for propane/LP gas, to equipment
shutoff valve (see Figure 18). Apply a
noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS
CONNECTIONS
1. Open equipment shutoff valve (see Fig-
ure 16).
2. For natural gas open main gas valve
located on or near gas meter. For pro-
pane/LP gas open propane/LP supply
tank valve.
3. Make sure control knob of heater is in the
OFF position.
119342-01B
4. Check all joints from equipment shutoff
valve to thermostat gas valve (see Figure
17 or 18). Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles forming
show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, page
14). Check all other internal joints for
leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, page 15).
8. Replace front panel.
Equipment
Shutoff Valve
Figure 16 - Equipment Shutoff Valve
Gas
Meter
Figure 17 - Checking Gas Joints for
Propane/LP
Supply Tank
Figure 18 - Checking Gas Joints for
www.desatech.com
Thermostat Gas Valve
Natural Gas
Thermostat Gas Valve
Propane/LP Gas
Open
Closed
Equipment
Shutoff Valve
Equipment
Shutoff
Valve
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vp16tbVn18tbVp26bVp16bVp26tbVn30b ... Show all

Table of Contents