TROUBLESHOOTING
Table 10.1: Control Board Blocking Error Codes (automatic reset):
"E"
CODE
SUPPLY SENSOR
E01
NOT CONNECTED
RETURN SENSOR
E02
NOT CONNECTED
DHW SENSOR
E04
NOT CONNECTED
E05
STACK SENSOR OPEN
E11
SUPPLY SENSOR SHORT
E12
RETURN SENSOR SHORT
E13
STACK SENSOR SHORT
E14
DHW SENSOR SHORT
COMMUNICATION ERROR
E19
E2PROM ERROR
E20
FALSE FLAME DETECTED
E21
HOT/NEUTRAL REVERSED
E22
POOR GROUND
E23
NET FREQUENCY ERROR
E24
POOR GROUND
E25
BLOCKED VENT
BLOCKED CONDENSATE
E26
DRAIN
E30
HIGH STACK TEMPERATURE
E31
LOW WATER
E32
HIGH RETURN TEMP
E42
INTERNAL HDWRE ERROR
E45
INTERNAL HDWRE ERROR
E46
INTERNAL HDWRE ERROR
E47
INTERNAL HDWRE ERROR
E48
INTERNAL HDWRE ERROR
RESET BUTTON ERROR
E51
PLEASE WAIT.
58
Downloaded from
www.Manualslib.com
Internal
Error Display
No.
51
52
55
57
59
60
65
63
0
35
44
43
45
46
38
41
39
36
40
47
31
32
33
34
66
manuals search engine
Error Description
Supply sensor not connected.
Return sensor not connected.
DHW sensor not connected.
Flue gas sensor open.
Supply sensor shorted.
Return sensor shorted.
Flue gas sensor shorted.
DHW sensor shorted.
Problems reading from or writing
to e2prom.
False Flame detected.
Phase and neutral of mains
supply are reversed.
No earth connected or internal
hardware error.
Mains frequency differs more
than 2% from 60Hz.
Earth connection is not ok.
Blocked Vent Switch is Open
Condensate drain blocked.
Flue gas sensor above max flue
setpoint + diff.
Water level is too low.
Return temperature is above
194°F (90°C).
Internal hardware error.
Internal hardware error.
Internal hardware error.
Internal hardware error.
Internal hardware error.
Reset button pressed more than
7 times within one minute.
Corrective Action
Check harness and sensor.
Check harness and sensor.
If DHW Mode is not intended to be set to Mode 1,
DHW Store with Sensor, then change it to the
appropriate Mode.
Check harness and sensor.
Check vent temperature, harness, sensor.
Check harness and sensor.
Check harness and sensor.
Check harness and sensor.
Check harness and sensor.
Contact PB Heat Representative.
Verify no flame in observation port. Check Sensor.
Verify polarity of incoming wiring. Check boiler
ground and harness.
Check boiler ground and harness.
Contact electrical provider and/or an electrician.
Check boiler ground and harness.
This error applies to PF-210 and PF-399 models.
Check for blocked vent pipe or blocked heat
exchanger. Check switch and tubing to switch.
Check condensate tanks, hoses, condensate switch,
and harness.
If flue pipe is hot, check flue temperature and
compare to values shown Table 8.6. Check for
proper gas input and combustion readings, check
for dirty heat exchanger.
If flue pipe is not hot, check flue sensor and
harness.
Check boiler water level, low water cut-off, harness.
If a LWCO is not used, a jumper should be placed
between terminals #9 and #10, LWCO Contact.
Check for reversed supply and return piping or
pump installed backwards.
Replace control.
Replace control.
Replace control.
Replace control.
Replace control.
Wait five minutes. If error does not clear, replace
control.