Common Alarms-What To Look For (Continued) - Pentair 920 Series Installation, Operating And Maintenance Instructions

Heat trace controller
Table of Contents

Advertisement

6.3 Common aLarms—What to LooK for (ContInued)
alarm
EEROM Data Failure
Contactor Count
(V3.11 and up)
INDUSTRIAL HEAT TRACING SOLUTIONS
description
This alarm indicates that the controller
has detected a failure in its nonvolatile
memory (this is where all of the controller's
configuration and calibration settings are
stored). This indicates an internal problem
and the HTC should be replaced and
returned to Pentair Thermal Managament
for repair.
This alarm indicates that the number of off-
to-on transitions of a contactor has exceeded
the CONTACTOR COUNT ALARM setting and
needs to be replaced.
EN- Raychem920series-IM-H56874       05/15
Cause of alarm
• The HTC cannot bypass the failed area of its memory
and has loaded factory defaults into this failed area.
• Contactor may be worn.
• Some configuration parameter (i.e. DEADBAND, AUTO
CYCLE INTERVAL, load shedding etc.) is causing the
contactor to toggle more than usual.
58 / 82