reset. All load-shedding parameters (including fail-safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
procedure: Enter the "Copy Configuration Sub-Menu" and select DEFAULTS TO A.
3.11.3 Copy defauLts to poInt b (v3.11 and up)
purpose: Loads the point-specific Pentair Thermal Managament default configuration
parameters, as defined in Appendix G, for Point B. As well, all of Point B's maintenance data are
reset. All load-shedding parameters (including fail safe) are configured with default values. The
CONSOLE SETPOINT MAXIMUM and MINIMUM are also configured with default values.
procedure: Enter the "Copy Configuration Sub-Menu" and select DEFAULTS TO B.
3.11.4 Copy poInt a to poInt b (v3.11 and up)
purpose: Copies the point-specific configuration parameters of Point A to Point B. Point A's
configuration parameters are not changed.
procedure: Enter the "Copy Configuration Sub-Menu" and select A TO B.
Important:
• To ensure that the TAGs for both points are not the same, Point A's TAG is copied, the last
character incremented by one, and then written to Point B's TAG.
• None of the communications addresses or the maintenance data values are copied.
3.11.5 Copy poInt b to poInt a (v3.11 and up)
purpose: Copies the point-specific configuration parameters of Point B to Point A. Point B's
configuration parameters are not changed.
procedure: Enter the "Copy Configuration Sub-Menu" and select B TO A.
Important:
• To ensure that the TAGs for both points are not the same, Point B's TAG is copied, the last
character incremented by one, and then written to Point A's TAG.
• None of the communications addresses or the maintenance data values are copied.