Mitsubishi Electric MXZ-32SV Service Manual page 21

Split-type, heat pump air conditioner inverter-controlled multi system
Hide thumbs Also See for MXZ-32SV:
Table of Contents

Advertisement

<Correction>
1 Suction super heat
(MIN gas pipe temperature thermistor - Evaporation temperature thermistor)
2 Each correction w 1
• (Each gas pipe temperature thermistor - Evaporation temperature thermistor)
• (Main pipe temperature thermistor - sub pipe temperature thermistor)
3 Discharge temperature
w 1 Perform this, when number of operation units is 2units or more
w 2 When the correction opening of suction super heat is 0, correct the LEV opening by dischaege temperature.
(1) LEV opening correction by suction super heat (COOL, DRY)
(Suction super heat) = (Minimum gas pipe temperature) - (Evaporation temperature)
When COOL and DRY , correct the LEV openings corrected from the table below
(2) Separate correction (COOL,DRY)
(When number of operation unit is 2 units or more)
(a) Correction by the separate super heat
Correct the LEV separately by temperature difference between each gas pipe temperature thermistor and evaporator
temperature thermistor.
1 Calculate each super heat of the unit from the expression below;
(Super heat) = (Gas pipe temperature thermistor) - (Evaporation temperature thermistor)
2 Select a minimum super heat from among them.
3 Correct an each LEV is corrected opening is corrected by difference between each super heat and minimum super
heat.
21
COOL
DRY
HEAT
-
w 2
w 2