9
Allow the system to run for 20 minutes� Wastewater should be running to the drain Air Gap (D) and
a pulsing / clicking sound should be heard coming from the Permeate Pump (C)� After 20 minutes,
close the Water Supply Inlet Valve (I) on the system manifold, then discharge water from the Faucet
(G) until Tank (E) is empty and water flow stops� The system is now cleansed and ready for use�
NOTE:
When starting the system for the first time, black/ gray water will flow from the bottle faucet for 30-60
seconds as the filter is purged�
Open the Water Supply Inlet Valve (I) and allow it to run until the tank is full� This may take over an
10
hour for the tank to fill completely� However, water can be used anytime after about 30 minutes
since the system produces and stores up to 4�25 gallons of water and can deliver water to both the
Wand and the Faucet even while it's making new water� The system capacity is about 25 gallons of
production per 8-hour work day�
1-1/2"
Drain Line
w/ Trap
from VistaPure
7A
Typical installation of drain Air Gap (S9145) using
existing sink drain system� Order separately�
7B
Typical installation of drain Air Gap (S9145) using
separate riser and trap� Order separately�
7C
Typical installation of drain Tee (S9146) using existing
sink drain system� Included with unit�
7D
Typical installation of dual inlet drain Air Gap system
(S9147) using branch tailpiece� Order separately�
NOTE:
Local codes vary greatly, so be sure to verify the preferred method prior to installation� Every VistaPure has a
pressurized drain discharge and multiple check valves in the system to prevent backflow from drain connections�
© 2000-2015 Vista Research Group, LLC. All rights reserved.
1-1/2"
w/ Trap
7A
Drain Line
from VistaPure
7B
Countertop
To Branch
Tailpiece
7D
Drain Line
from VistaPure
Airgap above
Flood Rim
Drain Line
from VistaPure
Drain Line from
Instrument Washer
1-1/2"
Pipe
7C
7