Off-Line Monitor Trouble(2)
Trouble
Printing is not normally carried out for
graph etc.
In processing for the time searching or
text convert of the operation status
monitor, "Date or Time is wrong" is
displayed
without
executing
processing.
It contains characters unable to be
fetched in (such as [ "or"] and the like).
Cause
-
The information inherent in a district
(language) will be added on the column of
Date and Time depending on the PC (OS)
the
of the district. However, such information
inherent in the district can not be read by
the maintenance tool.
data obtained by Ver.4.** has no
compatibility with that obtained by
Ver.3.**.
Please delete such special characters in
the file name.
Please set a setup of a printer as
Grayscale Printing.
- Change the setting of the OS to that in
English for use.
- Execute processing after deleting the
information (characters) inherent in the
district to be added on the column of Date
and Time.