Toshiba MMU-AP0152SH Service Manual page 53

Hide thumbs Also See for MMU-AP0152SH:
Table of Contents

Advertisement

7-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
Check code
Outdoor 7-segment display
Main
remote
central control
controller Check code
remote controller
Sub-code
E01
E02
E03
E04
E06
E06
No. of indoor
units which
received signal
normally
E07
E08
E08
Duplicated
indoor
addresses
E09
E10
Detected
Check code name
AI-NET
position
Remote
Communication error between
controller
indoor and remote controller
(Detected at remote controller side)
Remote
Remote controller sending error
controller
97
Indoor unit Communication error between
indoor and remote controller
(Detected at indoor side)
4
Indoor unit Indoor/outdoor communication
circuit error
(Detected at indoor side)
4
I/F
Decreased number of indoor units
I/F
Indoor/outdoor communication
circuit error
(Detected at outdoor side)
96
Indoor
Duplicated indoor addresses
I/F
99
Remote
Duplicated master remote
controller
controllers
CF
Indoor unit Communication error between
indoor P .C. board assembly
Status
Error detection condition
Corresponding
Communication interrupted
• Check remote controller inter-unit cable (A/B).
unit only stops.
between indoor P .C. board
• Check disconnection, connector contact error.
and remote controller.
• Check indoor power supply.
• Check indoor P .C. board error.
• Check remote controller address setup.
• Check remote controller P .C. board.
Corresponding
Signal could not be sent from
• Check the communication wire of remote controller: Exchange remote
unit only stops.
remote controller to indoor
unit.
Corresponding
No communication from
• Check remote controller and communication adapter wiring.
unit only stops.
remote controller (including
wireless) and communication
adapter.
Corresponding
Indoor unit does not receive
• Check power-ON order of indoor/outdoor.
unit only stops.
communication from outdoor
• Check indoor address setup.
unit.
• Check inter-unit cabling between indoor and outdoor.
• Check outdoor end terminal resistance setup (SW30-2).
• Check the power supply of indoor unit. (Power-ON)
All stop
When signal is not sent for a
certain period from the indoor
• Check connection of communication line between indoor and outdoor.
unit which has been used to
• Check connector connection for communication in indoor P .C. board.
send signals, [E06] is
• Check connector connection for communication in outdoor P .C. board.
normally displayed.
• Check indoor P .C. board failure.
• Check outdoor P .C. board (I/F) failure.
• Check outdoor terminator resistor setup (SW30-2).
All stop
Transmission from outdoor to
indoor cannot continue for 30
• Check the communication connection between indoor and outdoor.
seconds.
All stop
Multiple indoor unit address
• Check indoor address.
setup are duplicated.
• Check the change of remote controller connection (Group / individual)
Corresponding
In 2-remote controller control
• Check remote controller setup.
unit only stops.
(including wireless), both are
• Check remote controller P .C. board.
setup as master
(Header indoor unit stops and
other indoor unit is operating.)
Corresponding
There is any trouble in power
• Indoor P .C. board failure
unit only stops.
line.
Check item (position)
(When two remote controllers operate)
controller.
after setup of indoor address.

Advertisement

Table of Contents
loading

Table of Contents