SELECTING PIPE SIZE
The diameter of connection pipes differs according to the type and capacity of indoor units. Match the diam-
eters of connection pipes for indoor and outdoor units according to the following table.
Pipe size for indoor unit
Model name
Liquid pipe
09/12
Gas pipe
Liquid pipe
15/17
Gas pipe
Liquid pipe
24
Gas pipe
• If the diameter of connection pipes does not match the diameter of pipe end connections, use optional
different-diameter joints.
• When connecting the model 15 and 17 to either outdoor unit ı or Ç, use optional different-diameter joints
(MAC-454JP) because the valve size of gas pipes for the outdoor unit is ø9.52 mm (3/8 in.).
• When connecting the model 09 and 12 to either outdoor unit Å, use optional different-diameter joints (MAC-
455JP) because the valve size of gas pipes for the outdoor unit is ø12.7 mm (1/2 in.).
• When connecting the model 24 to outdoor unit Å, use optional different-diameter joints (MAC-456JP) be-
cause the diameter of pipes for the outdoor unit is ø12.7 mm (1/2 in.).
PIPE PREPARATION
1 If you use commercially available copper pipes, use the following table for pipe specifications.
Liquid pipe
Gas pipe
Gas pipe
Gas pipe
2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation.
3 Refrigerant pipe bending radius must be 100 mm (4 in.) or more.
CAUTION:
Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installa-
tion of the indoor unit and lack of thickness may cause dew drippage.
6
Allowable
connection pipe size
mm (in.)
ø6.35 (1/4)
ø6.35 (1/4)
ø9.52 (3/8)
ø9.52 (3/8)
ø6.35 (1/4)
ø6.35 (1/4)
ø12.7 (1/2)
ø12.7 (1/2)
ø6.35 (1/4)
ø6.35 (1/4)
ø15.88 (5/8)
ø15.88 (5/8)
Outside diameter
Minimum Wall thickness
mm (in.)
ø6.35 (1/4)
ø9.52 (3/8)
ø12.7 (1/2)
ø15.88 (5/8)
mm (in.)
Å UNIT
ı UNIT
Ç UNIT
mm (in.)
0.67 (0.0265)
0.72 (0.0285)
0.72 (0.0285)
0.80 (0.0315)
Valve size for outdoor unit
mm (in.)
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Insulation thickness
Insulation material
mm (in.)
8 (5/16)
Heat resisting from
8 (5/16)
plastic 0.045 Specific
8 (5/16)
gravity
8 (5/16)
ø6.35 (1/4)
ø12.7 (1/2)
ø6.35 (1/4)
ø9.52 (3/8)
ø6.35 (1/4)
ø9.52 (3/8)