Wiring; Ix Wiring - Crown Boiler CWD060 Installation Instructions Manual

Cwd series gas-fired direct vent hot water boilers
Hide thumbs Also See for CWD060:
Table of Contents

Advertisement

All wiring and grounding must be done in accordance with the authority having jurisdiction
or, in the absence of such requirements, with the national electrical code (ansi/nfpa 70) .
Disconnect electrical power to the boiler and heating system before servicing. Positively
assure that no voltage is present. Lock electrical boxes to prevent someone from
inadvertently restoring power before the heating system is safe to operate.
Never defeat or jump out safety devices.
Protect each boiler circuit with a properly sized over-current protection device.
Make electrical connections carefully according to the boiler's wiring diagram and
instructions.
Wire additional field supplied safety limits, such as low water cutoffs and temperature limit
devices, in series with the 120v circuit used to power the boiler. Do not alter the boiler's
factory wiring when adding an additional limit device.
1) Line Voltage (120 VAC) Field Connections – See Figure 9.0 for line voltage connections. Provide a dedicated circuit for the
boiler of 15A or greater. A service switch is recommended and is required by many local codes. Locate this switch in accor-
dance with local codes or, in the absence of any, in a location where it can be safely accessed in an emergency involving the
boiler. All 120VAC connections to the boiler itself are made inside the junction box on the right side of the boiler. 120VAC
connections are:
Ground
120VAC Hot (Black)
120VAC Neutral (White)
Heating Circulator Hot (Red)
Heating Circulator Neutral (White)
DHW Circulator Hot (Blue)
DHW Circulator Neutral (White)
The use of the Circulator outputs are as follows:
a) Heating Circulator - Pumps water upon a call for heat (CH) from a heating thermostat connected to the leads shown in
Figure 9.1 or from an EnviraCom thermostat.
b) DHW Circulator - Pumps boiler water to an indirect water heater upon a call for domestic hot water (DHW) from the
DHW thermostat terminals shown in Figure 9.1. This output can also be used for a second space heating zone. See Sec-
tion Xb of this manual for additional information.
Maximum circulator current draw is 5.0 FLA.
2) Low Voltage Connections – Low voltage field connections are located as shown in Figure 9.1 and are as follows:
a) Heating Thermostat - Connect to a 24 volt thermostat or other "dry contacts" (such as a zone panel end switch) that
close upon a call for heat. Follow thermostat manufacturer's instructions. To insure proper thermostat operation, avoid
installation in areas of poor air circulation, hot spots (near any heat source or in direct sunlight), cold spots (outside
walls, walls adjacent to unheated areas, locations subject to drafts). Provide Class II circuit between thermostat (or zone
controls) and boiler.
b) DHW - If used, connect to a 24VAC domestic hot water thermostat or 2nd space heating thermostat.
c) Option Plug - Used to connect Crown #761000 optional LWCO kit. If this kit is not installed, the factory supplied
jumper plug shown in Figure 9.1 must be installed for boiler to operate.
d) EnviraCOM - Used to connect an EnviraCom thermostat or other EnviraCom device approved by Crown to this boiler.
Section IX Wiring
WARNING
42
42