Setup - - Accessories
Filter Type:
MEDIA (i.e. TrueSenset)
S
EAC
S
MEDIA+EAC (i.e. TrueSenset)
S
CLEAN INTERVAL: 30 to 180 days (of actual blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies
to EAC filter selection only.
Humidifier Installed:
NO
S
YES
S
If YES, indicates to the system whether a humidifier is installed
and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default=12 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN:
NO (default)
S
YES
S
If YES, the humidifier will turn on if there is a humidify demand
present. The fan will turn on to Low speed if the fan setting is
Auto.
Ventilator:
NOTE: Only appears if ventilator is installed.
CLEAN INTERVAL:
60 to 180 days of actual operation (default=90)
S
Interval at which the Clean Ventilator Pre- -filter notification will
turn on.
UV Lights Installed
NO
S
YES
S
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
6 to 48 months operation time (default=12 months)
S
Interval at which the Change UV Lights notification will be
displayed.
Setup - - System Maintenance
Remind Owner of Routine Maintenance Every:
This setup is used to adjust the timer interval in which the normal
System Maintenance notification is turned on for the homeowner.
Range =
OFF
S
6 to 24 months, (default=12 months) Pressing the right
S
side button will reset the timer. Pop- -up confirmation will
be shown.
SYSTEM MAINTENANCE
REMIND OWNER OF
MAINTENANCE EVERY:
% USED:
< BACK
Fig. 32 - - System Maintenance
Setup - - Utility Saver
Cooling/Heat Pump Heating:
Turn off, Low Stage
S
12 MONTHS
50%
RESET >
A07033
This setup is available only if the equipment has a utility saver
input (refer to equipment Installation Instructions.) This setup
controls the response of the equipment when the utility saver input
is active.
The choices include:
Turn Off , (equipment turns off)
S
Low Stage (available if the AC/heat pump is a 2- -stage
S
model, runs low speed only)

CHECKOUT MENUS

CHECKOUT
FURNACE
HEAT PUMP HEATING
HEAT PUMP COOLING
HUMIDIFIER
VENTILATOR
BACK
Fig. 33 - - Checkout Menu
The Checkout menu will show the equipment installed in the
system. A sample checkout menu is shown in Fig. 33.
Checkout - - Furnace or Gas PAC
Make sure the furnace is properly installed before continuing.
LOW HEAT RUNTIME: 5 min.
S
HIGH HEAT RUNTIME: 5 min.
S
This menu item allows the furnace to be exercised. First, a low heat
runtime and high heat runtime are selected. Range = 5 - - 120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start- -up sequence. This
sequence will be displayed on the Evolution Zone Control screen.
After the gas valve and blower motor turn on, the screen will
automatically change to "FURNACE CHECK" and show the
current operating status of the furnace.
Checkout - - Electric Heat
ELECTRIC HEAT RUNTIME: 5 min., Default time = 5
S
min., Range = 0 - - 120 min.
If you have a fan coil with electric heaters, this menu item will
allow the heaters to be exercised.
With self- -identifying electric heaters, three stages of electric heat
are available to be exercised in any combination. Non- -identifying
heaters will only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised
then press START (right- -side button). The display will change to
show the fan coil's operating status.
Checkout - - Heat Pump Heating
HIGH HEAT RUNTIME: 5 min.
S
LOW HEAT RUNTIME: 5 min.
S
DEFROST: NO
S
The heat pump heating mode can be exercised with this menu
option. With a 2- -stage heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost
cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 - - 120 min.
NOTE:
Airflows during Checkout modes are fixed to the
Efficiency setting and are independent of other airflow settings. To
view airflows for normal heat pump heating mode, exit the
Checkout screen and apply a heating demand to the system.
Checkout - - Heat Pump Cooling or AC Cooling
HIGH COOL RUNTIME: 5 min.
S
LOW COOL RUNTIME: 5 min.
S
13