VENTILATION REQUIREMENTS (UNITED KINGDOM ONLY)
The appliance should be installed in a room or space with an air supply in accordance
with BS 5440:2 2000.
For rooms with a volume of less than 5 m
of at least 100 cm
For rooms with a volume between 5 m
free area of at least 50 cm
directly to the outside air, in which case no permanent ventilation is required.
For rooms with a volume greater than 10 m
Important !
Regardless of room size, all rooms containing the appliance must have direct ac-
cess to the outside air via an openable window or equivalent.
Where there are other fuel-burning appliances in the same room, BS 5440-2: 2000
should be consulted to determine the correct amount of free area ventilation require-
ments.
The above requirements also allow for use of a gas oven and grill, but you need to con-
sult a qualified engineer if there are other gas-burning appliances in the same room.
will be required.
2
will be required, unless the room has a door which opens
2
, permanent ventilation through a free area
3
and 10 m
, permanent ventilation through a
3
3
, no permanent ventilation is required.
3
15