Range - MGE UPS Systems 18/280 kVA Installation And User Manual

18÷280 kva
Table of Contents

Advertisement

2.2. R
ANGE
The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).
TYPE
CleanWave-18
CleanWave-30
CleanWave-40
CleanWave-55
CleanWave-90
CleanWave-140
CleanWave-180
CleanWave-220
CleanWave-280
1
According to European standards
2
If common conductor for neutral and earth (PEN conductor)
MGE UPS SYSTEMS
I
I
phase
neutral
Power.
max
Max
[kVA]
[A]
[A]
18
24
43
30
40
72
40
56
101
55
80
144
90
128
231
140
201
361
180
264
476
220
321
577
280
401
722
CleanWave - Installation and user manual
Version 2.1.4 – 15/01/2007 -
Total
losses
max
Phases
Neutral (N)
[W]
[mm²]
219
4
359
10
452
16
538
25
616
50
972
95
1212
150
1565
2x 95
1568
2x 95
Table 4
1
Minimum sections
Earth (PE)
( PEN
[mm²]
[mm²]
[mm²]
10
4
25
10
35
16
2x 25
16
2x 25
2x 50
25
2x 50
2x 95
50
2x 95
2x 150
95
2x 150
2x 185
95
2x 185
2x 240
95
2x 240
Page 5/13