Wall Hung Conversion - Smith GT-150 Installation, Operating And Maintenance Manual

Gt series
Table of Contents

Advertisement

Page 32

WALL HUNG CONVERSION

This boiler is certifi ed to be either mounted on the fl oor
as supplied, or mounted on a wall.
For wall mounting, perform the following steps.
1. Ensure that the desired location provides adequate
room for the clearance, see Table 1, venting, and
servicing.
2. Remove the right stainless steel panel, and
discard.
3. You will see that underneath the panel, the boiler frame
has mounting holes, designed for wall attachment.
4. The boiler must be mounted so the lag bolts enter
the studs of the wall. If this is not possible use a 3/4"
thick of plywood approximately 24 in, 610 mm, wide
by 36 in, 914 mm, high.
5. Install two #14-3" lag bolts three quarters of the
way into the surface, to the height you desire for
mounting.
6. Lift the boiler onto the wall, and tighten the top lag
bolts.
7. Once the unit is level, install the bottom two #14-3"
lag bolts.
8. Remove the Air Inlet Pipe assembly and Metering
elbow from the gas valve-venturi assembly, Figure
44.
Figure 44 - Air Inlet Pipe Removal
9. Remove the two screws attaching the gas valve-
venturi assembly to the side of the blower and rotate
the valve 90° so the 1/2" threaded connection is
pointing down, Figure 45. Pay close attention to how
the cork gasket is aligned.
Figure 45 - Gas Valve Rotation
NEW LOCATIONS
REMOVE SCREWS
AND ROTATE 90°
RE-INSTALL SCREWS
IN NEW LOCATIONS
GT INSTALLATION AND OPERATION INSTRUCTIONS
FOR SCREWS
1/2 IN THREADED
CONNECTION
10. Reattach the gas valve-venturi assembly to the side
of the blower making sure the gasket is correctly
orientated.
11. Re-install the Air Inlet Pipe assembly and Metering
elbow from the gas valve-venturi assembly, in the
vertical position, Figure 46.
Figure 46 - Air Inlet Pipe Installation
12. Install the gas line as per Figure 47 and follow
the instructions in the GAS PIPING section of this
manual.
Figure 47 - Gas Supply Piping

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt-200Pgt-150Pgt-200

Table of Contents