17.5.18. Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor current above 27.9A is detected by the current transformer (CT) in the
outdoor unit PCB.
Malfunction Caused:
1. Excessive refrigerant.
2. Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.