Specifications - Mitsubishi Electric PUMY-P200YKM Technical & Service Manual

Hide thumbs Also See for PUMY-P200YKM:
Table of Contents

Advertisement

3

SPECIFICATIONS

Service Ref.
Power source
Cooling capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor temp.
cooling
Outdoor temp.
Heating capacity
(Nominal)
Power input
Current input
COP
Temp. range of
Indoor temp.
heating
Outdoor temp.
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level
(measured in anechoic room)
Power pressure level
(measured in anechoic room)
Refrigerant
Liquid pipe
piping diameter
Gas pipe
FAN *2
Type x Quantity
Air flow rate
Control, Driving mechanism
Motor output
External static press.
Compressor
Type x Quantity
Manufacturer
Starting method
Capacity control
Motor output
Case heater
Lubricant
External finish
External dimension HxWxD
Protection devices High pressure protection
Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
* 1 Nominal cooling conditions
Indoor :
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
Outdoor :
35°C D.B. [95°F D.B.]
Pipe length :
7.5 m [24-9/16 ft]
Level difference :
0 m [0 ft]
*3 Liquid pipe diameter: 12.7 mm, in case of further piping length is longer than 60 m.
Note : 1. Nominal conditions * 1, * 2 are subject to ISO 15042.
2. Due to continuing improvement, above specifications may be subject to change without notice.
OCH575
*1
kW
kcal/h
*1
*1
BTU/h
kW
A
kW/kW
W.B.
D.B.
*2
kW
*2
kcal/h
BTU/h
*2
kW
A
kW/kW
D.B.
W.B.
dB <A>
dB <A>
mm (in)
mm (in)
m3/min
L/s
cfm
kW
%
kW
kW
mm
in
kg (lb)
* 2 Nominal heating conditions
20°C D.B. [68°F D.B.]
7°C DB/6°C W.B. [45 °F D.B./43 °F W.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
7
PUMY-P200YKM
PUMY-P200YKM-BS
380/400/415 V, 50 Hz
22.4
19,300
76,400
6.05
9.88, 9.39, 9.05
3.70
15 to 24°C
−5 to 46°C
25.0
21,500
85,300
5.84
9.54, 9.06, 8.74
4.28
15 to 27°C
−20 to 15°C
50 to 130% of outdoor unit capacity
15 - 250 / 12
56/ 61
-
9.52 (3/8)
19.05 (3/4)
Propeller Fan x 2
139
2,316
4,908
DC control
0.20 + 0.20
0
Scroll hermetic compressor x 1
Siam Compressor Industory Co., Ltd.
Inverter
Cooling 25 to100
Heating 17 to 100
5.3
0
FV50S(2.3litter)
Galvanized Steel Sheet
Munsell No. 3Y 7.8/1.1
1338 x 1050 x 330(+25)
52-11/16 x 41-11/32 x 13 (+1)
High pressure Switch
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor thermistor, Over current detection
Overheating, Voltage protection
R410A 7.3 kg
Electronic Expansion Valve
138 (305)
Cross Fin and Copper tube
HIC circuit
Reversed refrigerant circuit
BK01N339
BH79J199
Installation Manual
Joint pipe x 1, Grounded lead wire x2
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
*3
Unit converter
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm = m3/min x 35.31
lb = kg/0.4536
Above specification data is
subject to rounding variation.