Toshiba MMC-AP0157HP-E (TR) Service Manual page 79

Hide thumbs Also See for MMC-AP0157HP-E (TR):
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
code
P05
P05
P07
P07
P10
P10
P12
SVM-13085.indb 79
SVM-13085.indb 79
Location
Description
of
detection
Sub-code
I/F
Open phase detected,
Phase sequence error
SMMS (Series 1)
01: Open phase
detected
02: Phase
sequence error
SMMS-i
I/F
Detection of open
(Series 4)
phase / phase
00:
sequence
01: Compressor
Inverter DC voltage
1 side
(Vdc) error
02: Compressor
(compressor)
2 side
MG-CTT error
03: Compressor
3 side
01: Compressor
IPDU
Heat sink overheating
1 side
I/F
error
02: Compressor
2 side
03: Compressor
3 side
Detected indoor
Indoor
Indoor overflow error
address
unit
Indoor
Indoor fan motor error
unit
Error detection
System status
condition(s)
All stop
Phase sequence
error was detected
when the power is
turned on.
Open phase error
was detected
when the power is
turned on.
All stop
Open phase is
detected when
power is turned
on.
Inverter DC
voltage is too high
(overvoltage) or
too low
(undervoltage).
All stop
Temperature sensor
built into IGBT (TH)
is overheated.
All stop
Float switch
operates.
Float switch circuit
is open-circuited
or disconnected at
connector.
Stop of
Motor speed
corresponding
measurements
unit
continuously
deviate from target
value.
Overcurrent
protection is
activated.
– 79 –
FILE NO. SVM-13085
Check items (locations)
Check the phase sequence of
outdoor power wiring.
Check the outdoor PC board
(I/F) error.
Check for defect in outdoor
P.C. board (I/F).
Check power supply voltage.
Check outdoor fan system
error.
Check heat sink cooling duct
for clogging.
Check IGBT and heat sink for
thermal performance for faulty
installation.
(e.g. mounting screws and
thermal conductivity)
Check for defect in A3-IPDU.
(faulty IGBT built-in
temperature sensor (TH))
Check float switch connector.
Check operation of drain
pump.
Check drain pump circuit.
Check drain pipe for clogging.
Check for defect in indoor
P.C. board.
Check connection of fan
connector and wiring.
Check for defect in fan motor.
Check for defect in indoor
P.C. board.
Check impact of outside air
treatment (OA).
Check static pressure setting.
MG-CTT: Magnet contactor
12/24/13 10:56 AM
12/24/13 10:56 AM