Indoor Heat Exchanger Temperature Sensor (Open/Short) - Samsung AC030JN4DCH Service Manual

System air conditioner
Hide thumbs Also See for AC030JN4DCH:
Table of Contents

Advertisement

Troubleshooting

4-3-2 Indoor heat exchanger temperature sensor (open/short)

Indoor unit display
Symptom
Failure
Is the indoor heat exchanger
temperature sensor connector disconnected
from the PCB?
No
Remove the indoor heat exchanger
temperature sensor connector from
the PCB and measure the resistance
between two terminals
In this case, is the resistance
value out of range in the temperature table
on the right?
No
Restart the system after replacing the PCB
4-18
(Operation)
(Defrost) X (Timer) X (Filter)
Short or open circuit of indoor heat exchanger temperature sensor
Short or open circuit in the corresponding sensor
Yes
Restart the system after
connecting the connector to PCB
Yes
Failure of the indoor heat
exchanger temperature sensor
(replace)
<Temperature sensor
resistance value>
Current
Resistance
temperature
(kΩ)
(°C)
40
5.800
35
6.900
30
8.300
25
10.00
20
12.10
15
14.70
10
18.00
5
22.00
0
28.30
-5
33.90
-10
42.30
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac036jn4dchAc030jxscchAc036jxscch

Table of Contents