A M ethod for connecting wires
Connecting wires
A-unit
B-unit
Earth
Earth
terminal
terminal
Earth
Earth
terminal
terminal
Outdoor unit
Power cable to indoor units
Cable Type : A
Cable Type : B
Cable Type : C
Specification for circuit breaker and power supply cord
Power supply cord is not supplied with air conditioner.
Select the power supply cord in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
The specification for cables :
Main Power Supply Cable Indoor Power Supply Cable
Model
Specification
2
3G, 4.0 mm
AJ036JCJ5CH/
2
(0.0062 inch
) or
AA
more, H07RN-F
Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply, it must be
incorporated in a wire with a contact opening of ≥0.12inch.
C-unit
Indoor unit
Assembly cable
Earth
terminal
Earth
terminal
Main Power
Supply cable
Earth
terminal
Type
Specification
Type
2
3G, 1.0 mm
2
A
(0.0015 inch
)
B
or more, H07RN-F
D-unit
E-unit
Earth
Earth
terminal
terminal
Earth
Earth
terminal
terminal
Communication cable
to indoor units
Communication Cable
FUSE
Specification
Type
2
2G, 0.75 mm
2
(0.0011 inch
)
C
25 A
or more, H07RN-F
Type
MCCB
GL
Frame :
35 A
25 A
Trip : 25 A
13