Advance Planning; Power Supply - Monogram ZV48T Installation Instructions Manual

30", 36" and 48" professional vent hoods
Table of Contents

Advertisement

Advance Planning
ADVANCE PLANNING
Ductwork Planning
,These vent hoods are equipped for !0" round ductwork.
For best performance, use 10" round ductwork on the
48" wide hoods. 30" and 36" hoods mag be transitioned
to 8" round.
,This hood mag be vented verticallg through upper
cabinets, soffit or ceiling. A duct transition piece is
supplied for vertical exhaust. Use Iocallg supplied
elbows to vent horizontallg through the rear wall.
, Determine the exact location of the vent hood.
, Plan the route for venting exhaust to the outdoors.
, Use the shortest and straightest duct route possible. For
satisfactorg performance, duct run should not exceed
150 ft. equivalent length for ang duct configurations.
, Refer to "Duct Fittings" chart to compute the maximum
permissible length for duct runs to the outdoors.
, Use metal ductwork onlg.
, Install a wall cap or roof cap with damper at the exterior
opening. Order the wall or roof cap and ang transition
needed in advance.
, When applicable, install ang makeup (replacement)
air sgstem in accordance with local building code
requirements. Visit GEAppliances.com for available
makeup air solutions.
Wall Framing for Adequate Support
, These vent hoods are heavg. Adequate structural
support must be provided. Hoods must be secured to
vertical studs in the wall.
, It is stronglg recommend that the vent hood with duct
cover be on site before final framing and wall finishing.
This will also help to accuratelg locate the ductwork and
electrical service.
Decorative Duct Covers:
Decorative duct covers, 6" and 12" high, are available
to fit all models. The duct cover conceals the ductwork
running from the top of the hood to the ceiling or soffit.
Stack one or more duct covers over the top of the hood
to reach gour ceiling height.
POWER SUPPLY
IMPORTANT -(Please read carefullg)
,& WARNING
FOR PERSONAL SAFETY, THIS APPLIANCEMUSTBE
PROPERLY GROUNDED.
A AVERTISSEMENT POURDES
RA,SONS
DE S CUR,T ,
CET APPARE,
DO,T
aRE
CORRECTEMENT H IS/_ LA TERRE.
Remove house fuse or open circuit breaker before
beginning installation.
Do not use an extension cord or adapter plug with this
appliance. Follow National electrical codes or prevailing
local codes and ordinances.
Electrical
supplg
These vent hoods must be supplied with 120V, 60Hz, and
connected to an individual, properlg grounded branch
circuit, and protected bg a 15 or 20 amp circuit breaker
or time delag fuse.
. Wiring must be 2 wire with ground.
. If the electrical supplg does not meet the above
requirements, call a licensed electrician before
proceeding.
, Route house wiring as close to the installation location
as possible on the back wall or ceiling.
, Connect the wiring to the house wiring in accordance
with local codes.
Grounding
instructions
The grounding conductor must be connected to
a ground metal, permanent wiring sgstem, or an
equipment-grounding terminal or lead on the hood.
AWARN IN G
The improper connection of
the equipment-grounding
conductor can result in a risk
of electric shock. Check with a qualified electrician or
service representative if gou are in doubt whether the
appliance is properlg grounded.
AVERTISSEMENT
Le mauvais branchement du fil de mise (_ la terre peut
causer un choc 61ectrique. En cas de doute, consulter un
61ectricien qualifi6 ou un technicien pour d6terminer si
I'appareil est (3 la terre.